![ABB FBIP-21 BACnet/IP User Manual Download Page 46](http://html.mh-extra.com/html/abb/fbip-21-bacnet-ip/fbip-21-bacnet-ip_user-manual_4038046.webp)
Present value access
type
Default active/ Inact-
ive text
Description
Default object name
Object
ID
R
ON / OFF
Indicates if drive is
placed in BACnet Con-
trol Override by com-
manding BV18. In this
mode BACnet ac-
quires drive control
from its normal
source. Note that
HAND mode of the
panel has priority over
BACnet Control Over-
ride.
Control- Override-
Monitor
BV19
C
ENABLE / DISABLE
Command to start in-
terlock 1
Start- Interlock-1-
Command
BV20
C
ENABLE / DISABLE
Command to start in-
terlock 2
Start- Interlock-2-
Command
BV21
R
STARTED / NOT-
STARTED
Actual start status
Started- Monitor
BV24
R
Active / OK
Actual status of Safe
Torque Off
Safe-Torque-Off-Mon-
itor
BV25
R
UNDERLOAD / OK
Underload status
Underload-Monitor
BV26
R
OVERLOAD / OK
Overload status
Overload-Monitor
BV27
W
ON / OFF
Command to motor
heating mode
Motor-Heating-Com-
mand
BV28
R
ON / OFF
Actual status of motor
heating mode
Motor-Heating-Monit-
or
BV29
R
ON / OFF
User 0 status
User0- Monitor
BV30
R
ON / OFF
User 1 status
User1- Monitor
BV31
R
ON / OFF
User 2 status
User2- Monitor
BV32
R
ON / OFF
User 3 status
User3- Monitor
BV33
C
ON / OFF
User 0 command
User0- Command
BV34
C
ON / OFF
User 1 command
User1- Command
BV35
C
ON / OFF
User 2 command
User2- Command
BV36
C
ON / OFF
User 3 command
User3- Command
BV37
W
SAVE / NO
Parameter save com-
mand
Parameter- Save-
Command
BV39
W
Set1 / Set2
Command to Process
PID set1 or Process
PID set2 selection
PID-Set-Select
BV40
46 Communication protocol
Summary of Contents for FBIP-21 BACnet/IP
Page 2: ......
Page 4: ......
Page 8: ...8 ...
Page 14: ...14 ...
Page 38: ...38 ...
Page 50: ...50 ...
Page 58: ...58 ...
Page 62: ...62 ...
Page 71: ...Appendix D BACnet conformance certificate 23 Appendix D BACnet conformance certificate 71 ...
Page 72: ...72 Appendix D BACnet conformance certificate ...