![ABB FBIP-21 BACnet/IP User Manual Download Page 52](http://html.mh-extra.com/html/abb/fbip-21-bacnet-ip/fbip-21-bacnet-ip_user-manual_4038052.webp)
Function
Color
Name
Establishing communication to host
Blinking green
HOST
Connection to host OK
Green
Communication to host lost temporarily
Blinking red
Internal file system error. The error may be cleared by cycling drive
power. If the error persists, contact your local ABB representative.
Flashing orange, al-
ternating with the
MODULE flashing
orange
There is no power applied to the device.
Off
MODULE
Device is attempting to obtain IP configuration from the DHCP
server.
Flashing orange
Device is executing Duplicate Address Detection.
Orange
Device is waiting for a BACnet request.
Flashing green
Device has received a BACnet request within the timeout period.
Green
Ethernet link is down.
Flashing red
• Ethernet interface is disabled.
• Duplicate Address Detection may have detected a duplicate
address. Check the IP configuration and either initiate a Fieldbus
Adapter parameter refresh or cycle power to the drive.
or
• Drive is not supported by FBIP-21.
Red
Internal file system error. The error may be cleared by cycling drive
power. If the error persists, contact your local ABB representative.
Flashing orange, al-
ternating with the
HOST flashing or-
ange
Device is in boot mode, ready for firmware update (HOST led is
Off).
Flashing red/green
BACnet link is down.
Off
NETWORK /
NET
BACnet link is up at 100 Mbps.
Flashing green
Flashing indicates activity on interface.
BACnet link is up at 10 Mbps. Flashing indicates activity on interface.
Flashing orange
52 Diagnostics
Summary of Contents for FBIP-21 BACnet/IP
Page 2: ......
Page 4: ......
Page 8: ...8 ...
Page 14: ...14 ...
Page 38: ...38 ...
Page 50: ...50 ...
Page 58: ...58 ...
Page 62: ...62 ...
Page 71: ...Appendix D BACnet conformance certificate 23 Appendix D BACnet conformance certificate 71 ...
Page 72: ...72 Appendix D BACnet conformance certificate ...