![ABB FBIP-21 BACnet/IP User Manual Download Page 24](http://html.mh-extra.com/html/abb/fbip-21-bacnet-ip/fbip-21-bacnet-ip_user-manual_4038024.webp)
Default
Description
Name/Value
No.
47808 =
Shows the fieldbus adapter type as detected by the drive. You cannot
adjust this value.
FBA type
01
BACnet
This parameter is read-only.
Communication between the drive and the module is not established.
0 = None
BACnet
47808 = BACnet
-
This parameter is not used by the adapter module.
Reserved
02
0 = Auto
Sets the bit rate of the communication and determines if the commu-
nication can be simultaneously two-way (full duplex) or only one way
(half duplex).
Commrate
03
Auto-negotiate
0 = Auto
100 Mbps, full duplex
1 = 100 Mbps FD
100 Mbps, half duplex
2 = 100 Mbps
HD
10 Mbps, full duplex
3 = 10 Mbps FD
10 Mbps, half duplex
4 = 10 Mbps HD
1 = Dyn
IP DHCP
Sets the method for configuring the IP address, subnet mask and
gateway address for the Ethernet interface.
IP configuration
04
Configuration will be obtained from parameters 05…13.
0 = Static IP
Configuration is obtained via DHCP.
1 = Dyn IP DHCP
0
An IP address is assigned to each IP node on a network. An IP address
is a 32-bit number that is typically represented in “dotted decimal”
notation consisting of four decimal integers, in the range 0…255,
separated by periods. Each integer represents the value of one octet
(8- bits) in the IP address. Parameters 05…08 define the four octets
of the IP address.
IP address 1
05
IP address
0…255
…
…
…
…
0
See parameter 05 IP address 1.
IP address 4
08
IP address
0…255
24 Start-up
Summary of Contents for FBIP-21 BACnet/IP
Page 2: ......
Page 4: ......
Page 8: ...8 ...
Page 14: ...14 ...
Page 38: ...38 ...
Page 50: ...50 ...
Page 58: ...58 ...
Page 62: ...62 ...
Page 71: ...Appendix D BACnet conformance certificate 23 Appendix D BACnet conformance certificate 71 ...
Page 72: ...72 Appendix D BACnet conformance certificate ...