![ABB FBIP-21 BACnet/IP User Manual Download Page 32](http://html.mh-extra.com/html/abb/fbip-21-bacnet-ip/fbip-21-bacnet-ip_user-manual_4038032.webp)
For more information on scaling of analog outputs and inputs, see the firmware
manual.
BACnet access point
Description
Value
Drive parameter
AO0
Analog output 1 con-
trolled by fieldbus
AO1 data storage
13.12 AO1 source
AO1
Analog output 2 con-
trolled by fieldbus
AO2 data storage
13.22 AO2 source
AO0
Minimum value of signal
selected by parameter
13.12 AO1 source
0.0
13.17 AO1 source min
AO0
Maximum value of signal
selected by parameter
13.12 AO1 source
100.0
13.18 AO1 source max
AO1
Minimum value of signal
selected by parameter
13.22 AO2 source
0.0
13.27 AO2 source min
AO1
Maximum value of signal
selected by parameter
13.22 AO2 source
100.0
13.28 AO2 source max
Data point connections
The BACnet access points in the above drive parameter connections are linked to the
following data points:
Description
Drive parameter
BACnet access point
Storage parameter for
AO1
13.91 AO1 data storage
AO0
Storage parameter for
AO2
13.92 AO2 data storage
AO1
■
PID control
For PID control through BACnet/IP, configure the following drive parameters and set
the building controller supplied PID value(s) in the appropriate location:
BACnet access point
Description
Value
Drive parameter
AV43
Feedback 1 source data
storage
Feedback storage
40.08 Set 1 feedback 1
source
AV43
Feedback 2 source data
storage
Feedback storage
40.09 Set 1 feedback 2
source
AV42
Setpoint 1 source data
storage
Setpoint data storage
40.16 Set 1 setpoint 1
source
AV42
Setpoint 2 source data
storage
Setpoint data storage
40.17 Set 1 setpoint 2
source
32 Start-up
Summary of Contents for FBIP-21 BACnet/IP
Page 2: ......
Page 4: ......
Page 8: ...8 ...
Page 14: ...14 ...
Page 38: ...38 ...
Page 50: ...50 ...
Page 58: ...58 ...
Page 62: ...62 ...
Page 71: ...Appendix D BACnet conformance certificate 23 Appendix D BACnet conformance certificate 71 ...
Page 72: ...72 Appendix D BACnet conformance certificate ...