Description
Settings
Drive parameter
First part of the IP address
192
51.05 IP address 1
Second part of the IP address
51.06 IP address 2
Third part of the IP address
0
51.07 IP address 3
Last part of the IP address
51.08 IP address 4
Sets the network mask as
255.255.255.0, allowing access
only to the last subnet.
24
51.09 Subnet CIDR
Configures device object ID.
51.14 Device obj ID lo
Sets the communication timeout
as 30 seconds.
300
51.20 Comm loss time
The timeout feature monitors the
updating of the Control word and
Reference 1.
1 = Any message
51.21 Comm loss mode
Validates the FBIP-21 configura-
tion parameter settings.
1 = Configure
51.27 FBA A par refresh
Selects the Fieldbus A interface
as the source of start and stop
commands for external control
location 1.
12 = Fieldbus A
20.01 Ext1 commands
Selects fieldbus reference 1 as the
source for frequency reference 1.
4 = FB A ref1
28.11 Ext1 frequency ref1
1) Read-only or automatically detected/set
2) Example
Start-up 37