Mailbox function
The drive provides a Mailbox function to access parameters that have not been
pre-defined by the protocol. Using mailbox, any drive parameter can be identified and
read. Mailbox can also be used to adjust parameter settings by writing a value to any
parameter identified. The following table shows the mailbox objects.
Present
value access
type
Description
Default ob-
ject name
Object ID
W
Parameter number to be used by mailbox function.
Mbox-Param
AV25
W
Set (W) or indicate (R) of the data value of mailbox function.
Mbox-Data
AV26
To use the Mailbox function, write the parameter address to the Mbox-Param object
as a floating point value. The three lowest digits in the integer part are used for the
parameter index within the parameter group.
Example: For parameter 47.01, write the address as 47001.00 to the Mbox-Param
object. For parameter 47.999, write the address as 47999.00 to the Mbox-Param object.
Read or write the value to the Mbox-Data object as a floating point value. If the
parameter is a decimal type parameter, its value is shown as a decimal number. The
value of an integer type parameter is shown as an integer number.
Example: If parameter 47.01 has value 12.554 it is shown just as it is. If parameter 47.21
has value 125, it is shown just like that, without a decimal part.
Communication protocol 49
Summary of Contents for FBIP-21 BACnet/IP
Page 2: ......
Page 4: ......
Page 8: ...8 ...
Page 14: ...14 ...
Page 38: ...38 ...
Page 50: ...50 ...
Page 58: ...58 ...
Page 62: ...62 ...
Page 71: ...Appendix D BACnet conformance certificate 23 Appendix D BACnet conformance certificate 71 ...
Page 72: ...72 Appendix D BACnet conformance certificate ...