9
If a zone is set as conventional – no zone powered sounders fitted:-
Select Zone Sounder
Zn 2 =conventional
Up Dwn exit
Button 3-
Is Not available
Button 4- Up
increments to next zone.
Button 5- Dwn
decrements to previous
zone.
Button 6- exit
returns to menu system.
→
4 ISOLATE ZONE
–
If a fault occurs or work is being carried out on a zone, it is possible to disable that
zone without it affecting the other zones. Fire and fault activations from a disabled zone will be ignored.
----Select Zone-----
Zone = 1
Active
Toggle Up Dwn exit
Button 3- toggle
isolates/re-activates the
Zone.
Button 4- Up
increments to next Zone.
Button 5- Dwn
decrements to previous
Zone.
Button 6- exit
returns to menu system.
When a zone is isolated, the ‘Disabled’ and the specific zone fault LEDs are illuminated – eg. Zone1 is isolated.
→
5 ZONE SOUND TEST
–
Will momentarily sound any zone powered sounders if system is configured to
have zone powered on that zone.
Zn 1 = 2Wire
Test Zup Zdn exit
Note, isolated Alarm Sense Sounders cannot be tested.
Button 3- Test –
activates Alarm Sense
sounders on the zone for 3 seconds.
Test
not available if zone is conventional
or is isolated.
Button 4- Zup
increments to next Zone.
Button 5- Zdn
decrements to previous
Zone.
Button 6- exit
returns to menu system.