When engineers mode has been accessed, the initial entry point for the menu system is the same as that
for the user. Engineers access allows you to scroll UP and DOWN through the menu system..
11 Evacuate
→
12 ------EXIT------
13 Top of engineers
Silence Up Dwn Ok
Engineers access allows you to scroll
UP and DWN through the menu options.
The bottom line of the LCD shows the functions available with the buttons on which they are directly above.
Note, that buttons 1 & 2 have RESET and SILENCE BUZZER permanently assigned to them.
Button 1
– RESET
-
Returns the Fire Alarm System to a normal clear condition – Resetting fire alarm detectors,
silencing all sounders and resetting other devices connected to the control panel.
Button 2 -
SILENCE
-
Causes the internal buzzer during a Fire or Fault condition to stop sounding. Any
BUZZER
subsequent Fire or Fault condition will cause the buzzer to resound.
Button 3 -
SILENCE
-
Is used to turn off the external alarm sounders after a fire activation. The control
ALARMS
panel will however continue to indicate a fire condition and the internal buzzer will
continue to bleep. Any subsequent Fire activation will resound the external alarm
sounders.
When the alarm sounders have been ‘silenced’, the LCD option will show
‘Resound’.
Pressing Button 3 now, the external sounders will be turned back on and the LCD
option
reverts
back
to
‘
Silence’
.
Button 4 -
Up
-
Will take you up through the menu system. These are the User available options.
Button 5 -
Dwn
-
Will take you down through the menu system. Theses are the Engineer available options.
Button 6 -
OK
-
Is used to enter the menu choice which is highlighted on the LCD.
For example, pressing button 6 on the LCD shown above, ‘EXIT’ being the highlighted
option - would take you out of the menu system.
When exiting from engineers menu, switch the ‘Engineers’ switch to the ‘OFF’ position.
The available Engineers options are:-
14 - Wlktst All Zones
Walktest is conducted on all zones – can only test individual zones in user mode.
15 - Auxiliary Test
Allows Auxiliary relays to be tested
16 - Edit Patterns
Is where alarm, auxiliary and 2Wire sounder ‘Ringing’ patterns are setup.
17 - Assign Patterns
This is where ‘Ringing’ patterns are assigned to fire events
18 - Assign Class Pat
This is where a ‘Ringing’ pattern is assigned to Class Change.
19 - Assign Bomb Pat
This is where a ‘Ringing’ patterns is assigned to Bomb Alert.
20 - Assign Specl Pat
This is where a ‘Ringing’ patterns is assigned to Programmable Input.
21 - Assign Evac Pat
This is where a ‘Ringing’ patterns is assigned to Evacuate.
22 - Test Patterns
Allows you to test / verify the operation of a ‘Ringing’ pattern.
23 - Set Zone Config
Sets up the configuration of a zone ie, conventional / 2wire, latching / unlatching etc.
24 - Enter Zone Text
Allows zone description text to be edited.
25 - Edit User Text
Allows system description text to be edited.
26 - Blank
This function is currently unused.
27 - Setup Network
Sets up networking of panel to panel or other devices
28 - Event Log to PC
Down loads contents of event log to a PC.
29 - Data PC>Panel
Uploads data and panel settings from a PC to the panel.
30 - Data Panel>PC
Downloads data and panel settings from the panel to PC.
31 - Clear Event Log
Clears all previous events from the event log.
32 - Default Panel
Restores fire panel back to factory settings.
33 - Change User Code
Allows you to change the User access code.
34 - Level 3X Entry
35 - Exit
Returns you from the User menu back to the Fire system.