PANEL SPECIFICATION
Panel Order Code
FEUN-4
FEUN-8
FEUN-12
FEUN-16
No. of Zones
(25 detectors per zone max)
4 Zone
conventional /
2wire
8 Zone
conventional /
2wire
12 Zone
conventional /
2wire
16 Zone
conventional /
2wire
No. of alarm lines
4 (expandable to 16 programmed in groups of 4)
Maximum alarm load
Total = 1.25A. Maximum per line or circuit = 1A
Auxiliary outputs
•
Two sets of volt-free aux. programmable contacts (rated 2A @ 30V d.c.)
•
Two sets of volt-free fault contacts (rated 2A @ 30V d.c.)
Inputs
Class change, Bomb Alert and Programmable
Display
4 x 20 character LCD + zone fire and fault LED’s
Mains input voltage
10%, -6%. 50Hz
Output d.c. voltage
24V d.c. @ 250mA, 12V d.c @ 250mA
Battery size
12V 7AH x 2 (connected in SERIES)
Panel aesthetics
Metal back box with moulded polycarbonate front panel in cool grey
Panel dimensions (mm) hwd
469 x 373 x 103
Standby duration
Minimum 24 Hours (please contact technical sales for further information.)
Detector units
Apollo 60 and Orbis series smoke and heat with diode base. 220-680 Ohm call-
point
* For networking please specify the isolated CAN Network driver.
Alarm Sense (2-Wire) Specification.
Product code
FEWN-4
FEWN-8
FEWN-12
FEWN-16
No. of zones
4 Zone
8 Zone
12 Zone
16 Zone
Detectors per zone
25 maximum
25 maximum
25 maximum
25 maximum
Sounders per zone
25 maximum
25 maximum
25 maximum
25 maximum
Sounder current
Low
4ma
Medium
8ma
High
16ma
note [1]
Sounders per panel
200
160
80
note [1]
Inputs
Class change, Bomb Alert, Programmable
Display
4 x 20 character LCD + zone fire & fault LED’s and system LED’s
Mains input voltage
230 vac = 10% -6% 50Hz
DC output auxiliary voltage
24V d.c. @ 250mA, 12V d.c @ 250mA
Battery size
12V 7AH x 2 (connected in SERIES)
Battery standby
Minimum 24 Hours (please contact technical sales for further information.)
Panel dimensions (mm) hwd
469 x 373 x 103
Programmable features
Extensive via buttons and LCD display
CAN Network
Panel and repeater combinations via CAN 2.0b link
Ancillary outputs:
Alarm Lines
4
note [2]
Alarm current total
Is 1.25A-Zone Sounder Current note [3]
Auxiliary outputs
2 sets of volt free contacts, rated @ 2A 30Vdc
Fault outputs
2 sets of volt free contacts, rated @ 2A 30Vdc
Notes.
[1] – Current is dependent on sound level and tone outputs. Total current must not exceed 80 high output sound
levels. Or 200 low output sound levels.
[2] – Alarm lines – AL1 to AL4.
[3] – Total Panel Alarm Current is 1.25A, therefore zone sounder current must be taken into account when
deciding how much loading is allowed on Alarms AL1 to AL4.
Alarmsense is a registered trade name of Apollo Fire Detectors Ltd.