3) The panels can now be networked to each other:- through
Set up net devices
At Panel address No1, connect to it, the Panel address no2.
My Adrs 1 Mode:Star
CONNECT? 2 = P Y
Toggle
Up down exit
The top line shows the address of this
panel is 1 and is connected in Isolated
Star configuration
At address 2 there is a Panel (P), which
is connected (Y) to this panel.
Pressing button3 toggle will connect /
disconnect panel2 (this is indicated by
the ‘Y’ or ‘N’.)
At Panel address No2, connect to it, the Panel address no1.
My Adrs 2 Mode:Star
CONNECT? 1 = P Y
Toggle
Up down exit
The top line shows the address of this
panel is 2 and is connected in Isolated
Star configuration
At address 1 there is a Panel (P), which
is connected (Y) to this panel.
Pressing button3 toggle will connect /
disconnect panel2 (this is indicated by
the ‘Y’ or ‘N’.)
→
28 EVENT LOG TO PC
–
This sends the event (history) log to a PC.
ONLY SELECT THIS OPTION WHEN THE PC IS SET UP AND READY TO RECEIVE DATA FROM THE
PANEL.
An Emergi-Lite Converter Cable is Required.
Prior to sending data to the PC, connect the Converter Cable from the ‘PC PORT’ connection on the Eurofire EN54
PCB to the COM port of the PC.
A program such as ‘HyperTerminal’ is required to connect the PC to the Eurofire EN54 panel. The settings on
‘HyperTerminal’ for the connection are:-
Bits Per Sec = 4800,
Data Bits = 8,
Parity = None,
Stop Bits = 1,
Flow Control = None.
In ‘HyperTerminal’ choose the ‘Transfer’ tab and then select ‘Capture Text’, select a name and location where the file
is to be saved.
Once the PC is set up to receive data from the Eurofire EN54 panel
Then select
→
28 EVENT LOG TO PC
The event log will now be sent to the PC.