Panel Operation
Normal Condition
In the normal condition, the LCD will display:-
EMERGI-LITE TnB
Scanning 16 Zones
14:42 Thu 6 Nov 2003
Line 1-
User Display Message. This is
set on commissioning.
Line 2-
Displays the number of detection
zones on the fire panel.
Line 4-
Displays Time.
Fire Condition
In the event of a fire activation, the panel will sound the internal buzzer and activate the external alarm
sounders in the sequence pre-programmed at the commissioning stage. The ‘GENERAL FIRE’ and the
relevant zone fire LEDs will be illuminated. i.e Zones 1,2 & 4 are in fire.
FIRE 1of 3
zone 1 in fire
Last Fire = 3
zone 4 in fire
Line 1-
Shows which fire is being
displayed on line 2 and the total number
of fire detected.
Line 2-
Alternates between the zone
number and the zone description of the
fire.
Using
buttons 4&5
you can scroll and
display all fires individually on line 2.
Line 3-
Shows last fire that has occurred
which is also the total number of fires.
Line 4-
Alternates between the zone
number and the zone text of the last fire.
Fires signalled from Networked Panels are shown in the same way as local fires but also show the network
address of the panel where the fire was detected as well as the zone number eg.
FIRE 1of 3
FIRE-Panel 3 Zn1
Last Fire = 3
FIRE-Panel 3 Zn4
To silence external sounders -
- Enter User Code, then press Button 3 – SILENCE ALARMS.
To resound external sounders (only allowed if sounders have been silenced first) -
- Enter User Code, then press Button 3 – RESOUND.
To silence the panel internal buzzer -
- Enter User Code, then press Button 2 – SILENCE BUZZER.
To reset the panel -
- Enter User Code, then press Button 1 – RESET.