30
This would be set up as shown:-
NetAdd
→
4
Delay 30
Pulse 90 On2 Off2
Pattern time 1890
Item Up Dwn Back
Netadd = network address No4 (where
the pattern will be activated.)
Delay = 30 Seconds.
Pulse time = 90 Seconds.
(alarms will be pulsed for 90-30=60 sec)
At a rate of :-
On time = 2 sec Off time = 2sec.
Pattern Time = 1890
(which is 1890-90=1800sec or 30mins).
The Eurofire control panel is supplied with the following settings as default:-
Conventional - FEUN
Pattern
Device
Period
Where
Assigned
to
Ptrn 0
Alarms 1,2,3,4
Continuous
Evacuate & Class Change
(NetAdd=0; Delay=0; Pulse=0; On=1; Off=0; Pattern Time=CONT)
Ptrn 1
Alarms 1,2,3,4
Pulsing (1sec on/off)
Bomb Alert
(NetAdd=0; Delay=0; Pulse=CONT; On=1; Off=1; Pattern Time=CONT)
Ptrn 2
Alarms 1,2,3,4 & Auxiliary Relay Continuous
All Zones
(NetAdd=0; Delay=0; Pulse=0; On=1; Off=0; Pattern Time=CONT)
Alarm Sense - FEWN
Pattern
Device
Period
Where
Assigned
to
Ptrn 0
Alarms 1,2,3,4
Continuous
Evacuate & Class Change
(NetAdd=0; Delay=0; Pulse=0; On=1; Off=0; Pattern Time=CONT)
Ptrn 1
Alarms 1,2,3,4
Pulsing (1sec on/off)
Bomb Alert
(NetAdd=0; Delay=0; Pulse=CONT; On=1; Off=0; Pattern Time=CONT)
Ptrn 2
Alarms 1,2,3,4 & Auxiliary Relay Continuous
All Zones
(NetAdd=0; Delay=0; Pulse=0; On=1; Off=0; Pattern Time=CONT)
Ptrn 3
All Zone Sounders
Continuous
All Zones, Evacuate, Class Change
(NetAdd=0; Delay=0; Pulse=0; On=1; Off=0; Pattern Time=CONT)
Ptrn 4
All Zone Sounders
Pulsing (1sec on/off)
Bomb Alert
(NetAdd=0; Delay=0; Pulse=CONT; On=1; Off=0; Pattern Time=CONT)
In order to set up patterns:-
1)
Decide on how the pattern is to operate:-
Delays, Continuous or Pulsing, devices to be active, network address of where the pattern is to ring etc.
2)
Check what patterns are currently active on the panel – use menu options 16 ‘edit patterns’ and 17
‘assign zn pttrns’.
3)
Using option 16 ‘EDIT PATTERNS’.
Create the required pattern or patterns.
4)
Once all patterns have been created, assign them to the zones that they are to be activated from – use
option 17 ‘ASSIGN ZN PTTRNS’. Any number of patterns can be assigned to any or all of the zones.
→
17 ASSIGN ZN PTTRNS
–
Assigns patterns to a zone or number of zones. When a fire is detected on a zone, the patterns assigned to that
zone will operate as per the pattern programming from Option 16 EDIT PATTERN.
Selct Zone + Pattern
Zone 1 Pattern 0
ACTIVE
tggle Zup Pup exit
Shows that when Zone 1 is in fire
Pattern 0 will Activate.
Button 3 –
tggle
will make the pattern
Active or Unused for that zone.
Button 4 –
Zup
moves to next zone.
Button 5 –
Pup
moves to next pattern.
Button 6 –
exit
returns back to menu
system saving the settings at same time.
Please note, any or all of the patterns can be assigned to any or all of the zones.