16
Clause 45.4 Inspection and Test of a System Over a 12 Month Period
•
The switch mechanism of every manual call point should be tested.
•
Every automatic fire detector should be examined and functionally tested. Note: this includes, but is not
limited to; smoke detectors, most heat detectors, optical beam smoke detectors, aspirating fire detection
systems, carbon monoxide fire detectors and flame detectors.
•
Additional checking is required for some analogue fire detectors and for multi-sensor detectors.
•
All fire alarm devices should be tested.
•
Certain filament lamps should be replaced.
•
Radio fire detection and fire alarm system signal strengths should be checked.
•
Visual inspection of readily accessible cable fixings should be undertaken.
•
The cause and effect programme should be checked.
•
The standby power supply capacity should be checked.
•
Other annual checks and tests recommended by the system component manufacturers should be
undertaken.
•
Outstanding defects should be reported and the servicing certificate issued.
Clause 46.4.4 Recommendations for action to address an unacceptable rate of false alarms
•
This Clause recommends that any false alarm investigation and subsequent modifications to the system
takes into account the guidance provided in Section 3 of BS5839-1 : 2002. Note: Any organisation
undertaking false alarm investigations and related remedial work should be able to demonstrate their
competence to undertake such work.
Section 3 of BS5839-1 : 2002
•
This section contains comprehensive information on all aspects of limitation of false alarms. The
measures to limit false alarms are divided into eight groups:
•
Siting and selection of manual call points.
•
Selection and siting of automatic fire detectors.
•
Selection of system type.
•
Protection against electromagnetic interference
•
Performance monitoring of newly commissioned systems.
•
Filtering measures.
•
System management.
•
Regular servicing and maintenance.