29
For example, pattern 1 consisting of all alarms and Auxiliary relay is to be activated at another panel whose network
address is no 2. The pattern should be alarms1,2,3&4 and auxiliary relay on until reset (one out-all out situation)
without there being a delay to activation.
1)
Set pattern 1 and alter devices until Alarms 1, 2, 3, 4 and Aux. Relay:-
Pattern 1
→
Alarms 1 2 3 4 Aux
Pattern Details
Item Up Dwn Exit
→
Indicates that pattern devices are
being edited.
Button 3 Item
, Moves pinter(
→
)
to next
line.
Button 4 Up
, Alters devices upwards.
Button 5 Dwn,
Alters devices
downwards.
Button 6 Exit,
Exits from editing
patterns.
When pattern number and devices are correct, Press button3 (Item) until at,
→
Pattern Details.
Then press button 5 (Edit) ie.
Pattern 1
Alarms 1 2 3 4 Aux
→
Pattern Details
Item Edit Exit
2)
Set pattern details to NetAdd 2, delay 0, Pulse 0, On 1, Off 0 and Pulse Time CONT:-
NetAdd
→
2
Delay 0
Pulse 0 On1 Off0
Pattern time CONT
Item Up Dwn Back
→
Indicates option to be modified.
Netadd = network address No2 (where
the pattern will be activated.)
Delay = 0 Seconds.
Pulse time = 0 Seconds.
(alarms will be pulsed for 0 sec)
On time = 1 sec Off time = 0sec.
Pattern Time = CONT (until reset.).
Button 3 Item
, Moves
→
to next option.
Button 4 Up
, Increments option being
pointed to.
Button 5 Dwn
, Decrements option being
pointed to.
Button 6 Exit,
Exits from editing pattern
the pattern details.
The pattern must then be assigned to a zone or number of zones – this is done in option
17 ASSIGN ZN PTRNS.
Therefore when a zone goes into fire, all patterns that are assigned to that zone will be activated.
A more complex pattern would be for example:-
The pattern has a 30 second delay, then pulses for 60 seconds with a period of 2 seconds On and 2 seconds Off. The
alarms are then to be On for 30 minutes (1800 seconds). The pattern is to be active on panel 4.