1 3 A D D I N G/R EP L AC I N G A U P S M O D U L E
INVERTER MODE
LED indicators status on all operating modules
Display on all operating modules
LED INDICATION
COLOR
SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier
Green
Bypass
Green
Load
Green
Battery
Green
BYPASS MODE (ECO MODE)
LED indicators status on all operating modules
Display on all operating modules
LED INDICATION
COLOR
SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier
Green
Bypass
Green
Load
Yellow
Battery
Green
13.2.2 Insert the module in the frame
In a redundant parallel system one module can be
reintroduced in its original location without af-
fecting the normal system operation. The load
will be protected by the other modules running in
INVERTER or STATIC BYPASS mode.
The module must be previously set according to
system personalization. Please contact your near-
est service center for correct settings.
1. Remove UPS module compartment protec-
tion cover by unscrewing the two fixing
screws on the front.
2. Make sure that the “Battery breaker” of the
slot where the module need to be inserted is
turned to OFF position (opened).
3. Slide two thirds of UPS module into dedi-
cated UPS compartment (make sure not to
plug the UPS module into the rear connector).
Push UPS module to its final position and
push firmly to assure correct contact on the
rear plugs.
NOTE
WE RECOMMEND 2 PEOPLE FOR
INSERTION OF THE MODULE INTO THE
FRAME. THE WEIGHT OF ONE MODULE IS
APPROXIMATELY 66 KG
4. Fix the UPS module with the two screws at
the front and tighten them with a torque of 6
Nm.
LED indicators status on the module
Display on the module
LED INDICATION
COLOR
SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier
Green
Bypass
Green
Load
Yellow
Battery
Flashing red