Block
Terminal
Contact
Signal
On Display
Function
X2
X2 / 18
C
NC
NO
-
Common
X2 / 17
-
Relays AUX
(Function on request, to be defined)
X2 / 16
-
X2 / 15
C
NC
NO
COMMON_ALARM
Common
X2 / 14
ALARM
No Alarm Condition
X2 / 13
Common Alarm (System)
X2 / 12
C
NC
NO
LOAD_ON_MAINS
Common
X2 / 11
Message
No Load on Bypass
X2 / 10
Load On Bypass (Mains)
X2 / 9
C
NC
NO
BATT_LOW
Common
X2 / 8
ALARM
Battery Ok
X2 / 7
Battery Low
X2 / 6
C
NC
NO
LOAD_ON_INV
Common
X2 / 5
Message
No Load on Inverter
X2 / 4
Load on Inverter
X2 / 3
C
NC
NO
MAINS_OK
Common
X2 / 2
ALARM
Mains Failure
X2 / 1
Mains Present
X1
X1 / 2
-
EXT_MAN_BYP
Interlock Function
Max. 30Vdc/2A; 60Vdc/0.7A
(Ext Manual Bypass) / 2AT
X1 / 1
-
5.3.2
Output dry port (X2 and X1)
X2 terminals can hold Cable from 0.2mm2 – 1.5mm2
X2 are potential free contacts and are rated: Max 250Vac/8A; 30Vdc/8A; 220Vdc/0.12A
5 CO N T R O L & M O N I TO R I N G