3 System description
The DPA 250 S4 is a 3 ph transformer less Uninter-
ruptible Power System (UPS). It is a true modular
on-line double conversion UPS with a perfor-
mance qualification code VFI-SS-111 providing
quality power for sensitive equipment.
It is a modular UPS system consisting of:
•
DPA 250 S4 UPS Frame, max rated power of
250kW (N+1)
•
Up to 6 x DPA 250 S4 UPS modules, rated
power 50 kW
•
Bottom/Top cable entry including incoming
/ outgoing and battery terminals
•
Maintenance bypass switch (optional)
•
System graphical display (optional)
•
Parallel kit and cable (5mt) (optional)
•
Communication interfaces
—
3.1 DPA 250 S4 UPS
The DPA 250 S4 frame has 6 configuration as
follow:
Description
Configuration
Bottom cable entry (BCE)
UPS DPA 250 S4 F250-6 BCE SP
Version with built-in MBS available
UPS frame is equipped with system graphical display, par-
allel kit and cable, up to 6 x UPS Module slots (N+1).
Suitable for parallel system configuration.
UPS DPA 250 S4 F250-6 BCE P
Version with built-in MBS available
UPS frame is equipped with parallel kit and cable, up to 6 x
UPS Module slots (N+1).
Suitable for parallel system configuration.
UPS DPA 250 S4 F250-6 BCE S MBS
UPS frame is equipped with system graphical display, main-
tenance bypass switch (MBS), up to 6 x UPS Module slots
(N+1).
Suitable for standalone configuration.
Top cable entry (TCE)
UPS DPA 250 S4 F250-6 TCE SP
Version with built-in MBS available
UPS frame is equipped with system graphical display, par-
allel kit and cable, up to 6 x UPS Module slots (N+1).
Suitable for parallel system configuration.
UPS DPA 250 S4 F250-6 TCE P
Version with built-in MBS available
UPS frame is equipped with parallel kit and cable, up to 6 x
UPS Module slots (N+1).
Suitable for parallel system configuration.
UPS DPA 250 S4 F250-6 TCE S MBS
UPS frame is equipped with system graphical display, main-
tenance bypass switch (MBS), up to 6 x UPS Module slots
(N+1).
Suitable for standalone configuration.
3.1.1
DPA 250 S4 UPS Frame types