DPA 2 50 S 4 50 - 2 50 K W
O P ER AT I N G M A N UA L
—
9 Installation
9.1.1
Climatic conditions
Ambient temperature
°C
0 to +40
Relative Humidity
%
< 95
Conditions of condensation
No
Condition of wind-driven rain, snow, hail, etc.
No
Conditions of water from sources other than rain
No
Condition of icing
No
The climate-controlling system could be periodically switched on or off but extremely high or low temperature shall be
prevented.
9.1.2
Biological conditions
Flora (presence of mold, fungus)
No
Fauna (presence of rodents and other animals)
No
The location shall not have particular risks of biological attacks
9.1.3
Mechanical active substance
The UPS shall not be placed in proximity to source of sand or dust.
9.1.4
Chemical active substance
Location with normal level of contaminants experienced in urban areas over the whole area.
9.1.5
Mechanical conditions
The UPS shall be placed in areas with insignificant vibration and shock
—
9.1 Environmental condition
The UPS is designed to be installed indoor, in temperature-controlled rooms. Heating, cooling, forced
ventilation and humidification are used to maintain the conditions as shown in the next sub chapters: