Electrical installation 83
5. Make sure that all power is disconnected and reconnection is not possible. Use proper
safe disconnect procedures according to local codes.
6. Run the input cables from the supply source to the cabinet. Ground the cable shields
360° at the lead-through plate.
7. Twist the cable shields of the input cables into bundles and connect them and any
separate ground conductors or cables to the drive module ground terminal or to the
cabinet PE busbar.
8. Connect the phase conductors of the input cables to terminals L1/U1, L2/V1 and
L3/W1 of the drive module. For the tightening torques, see page
.
DC connection
The UDC+ and UDC– terminals are intended for common DC configurations of a number
of drives, allowing regenerative energy from one drive to be utilized by the other drives in
the motoring mode. See
ACS880-01 drives and ACS880-04 drive modules common DC
systems application guide
(3AUA0000127818 [English]).
Overview of control cable connection process
This table lists the main steps of the control cable connecting process.
Step
Section
Page
1
Removing the control panel holder from the external control unit
2
Attaching the control cable clamp plate
3
Connecting the external control unit to the drive module
4
Connecting the control cables to the terminals of the control unit
Summary of Contents for ACS880-04F
Page 1: ...ABB industrial drives Hardware manual ACS880 04F drive modules ...
Page 4: ......
Page 24: ...24 Introduction to the manual ...
Page 46: ...46 Guidelines for planning the mechanical installation ...
Page 102: ...102 Installation checklist ...
Page 106: ...106 Fault tracing ...
Page 135: ...Technical data 135 Declaration of Conformity ...
Page 136: ...136 Technical data ...
Page 140: ...140 Technical data ...
Page 142: ...142 Dimension drawings Standard configuration IP20 UL Open Type ...
Page 143: ...Dimension drawings 143 Drive module with options E208 and H370 IP20 UL Open Type ...
Page 144: ...144 Dimension drawings Drive module with options 0B051 E208 0H371 IP00 UL Open Type ...
Page 145: ...Dimension drawings 145 Drive module with options 0B051 E208 0H371 C217 IP00 UL Open Type ...
Page 146: ...146 Dimension drawings Drive module with options 0B051 0H371 IP00 UL Open Type ...
Page 147: ...Dimension drawings 147 Mounting plate 3AXD50000038119 ...
Page 148: ...148 Dimension drawings 3AXD50000038119 ...
Page 149: ...Dimension drawings 149 External control unit 3axd50000011687 ...
Page 150: ...150 Dimension drawings ...
Page 164: ...164 Safe torque off function ...