Technical data 127
Losses, cooling data and noise
The cooling air temperature rises 30 degrees Celsius (86 °F) when it goes through the
drive module if the temperature of the input cooling air is 40 degrees Celsius (104 °F).
Terminal and lead-through data for the power cables
The maximum accepted cable size is 4 × (3 × 240) mm
2
or 4 × (3 × 500 AWG). Screw size
for connecting busbars to the drive module input and output busbars: M12, tightening
torque 50...75 N·m.
Units without full-size output cable connection terminals (+0H371)
and with a common mode filter (+E208)
It is possible to use the maximum cable size (4 × [3 × 240] mm
2
or 4 ×[(3 × 500 AWG]) only
with special cable lugs and additional insulation. For more information, contact your local
ABB representative.
Terminal data for the control cables
See page
Drive type
Frame size
Air flow
Heat dissipation
Noise
Heatsink
Front
Heatsink
Front
m
3
/h
m
3
/h
W
W
dB(A)
U
N
= 400 V
ACS880-04F-504A-3
R11
1400
120
5100
550
75
ACS880-04F-584A-3
R11
1400
120
5800
650
75
ACS880-04F-649A-3
R11
1400
120
7400
750
75
ACS880-04F-725A-3
R11
1400
120
7950
850
75
ACS880-04F-820A-3
R11
1400
120
8950
950
75
ACS880-04F-880A-3
R11
1400
120
9600
1000
75
U
N
= 500 V
ACS880-04F-459A-5
R11
1400
120
3900
550
75
ACS880-04F-502A-5
R11
1400
120
5050
600
75
ACS880-04F-582A-5
R11
1400
120
5750
700
75
ACS880-04F-634A-5
R11
1400
120
7350
800
75
ACS880-04F-715A-5
R11
1400
120
7900
900
75
ACS880-04F-820A-5
R11
1400
120
8900
1000
75
ACS880-04F-880A-5
R11
1400
120
10050
1050
75
Electrical power network specification
Voltage (
U
1
)
ACS880-04F-xxxx-3 drive modules: 380…415 V AC phase
+10%/-15%. This
is indicated in the type designation label as typical input voltage level
3
400 V AC.
ACS880-04F-xxx-5 drive modules: 380...500 V AC 3-phase
+10%/-15%. This
is indicated in the type designation label as typical input voltage levels
3
400/480/500 V AC.
Network type
TN (grounded) and IT (ungrounded) systems
Short-circuit withstand
strength (IEC 61439-1)
Maximum allowable prospective short-circuit current is 65 kA when by the
fuses given in the fuse table. For the maximum allowable prospective short-
circuit current with circuit breakers, see section
Protecting the drive and input
on page
~
~
Summary of Contents for ACS880-04F
Page 1: ...ABB industrial drives Hardware manual ACS880 04F drive modules ...
Page 4: ......
Page 24: ...24 Introduction to the manual ...
Page 46: ...46 Guidelines for planning the mechanical installation ...
Page 102: ...102 Installation checklist ...
Page 106: ...106 Fault tracing ...
Page 135: ...Technical data 135 Declaration of Conformity ...
Page 136: ...136 Technical data ...
Page 140: ...140 Technical data ...
Page 142: ...142 Dimension drawings Standard configuration IP20 UL Open Type ...
Page 143: ...Dimension drawings 143 Drive module with options E208 and H370 IP20 UL Open Type ...
Page 144: ...144 Dimension drawings Drive module with options 0B051 E208 0H371 IP00 UL Open Type ...
Page 145: ...Dimension drawings 145 Drive module with options 0B051 E208 0H371 C217 IP00 UL Open Type ...
Page 146: ...146 Dimension drawings Drive module with options 0B051 0H371 IP00 UL Open Type ...
Page 147: ...Dimension drawings 147 Mounting plate 3AXD50000038119 ...
Page 148: ...148 Dimension drawings 3AXD50000038119 ...
Page 149: ...Dimension drawings 149 External control unit 3axd50000011687 ...
Page 150: ...150 Dimension drawings ...
Page 164: ...164 Safe torque off function ...