Safety instructions 17
WARNING!
Obey these
instructions. If you ignore them, equipment malfunction
and damage to the fiber optic cables can occur.
•
Handle the fiber optic cables with care.
•
When you unplug the cables, always hold the connector, not the cable itself.
•
Do not touch the ends of the fibers with bare hands as the ends are extremely
sensitive to dirt.
•
Do not bend the fiber optic cables too tightly. The minimum allowed bend radius is
35 mm (1.4 in).
Grounding
These instructions are for all personnel who are responsible for the grounding of the drive.
WARNING!
Obey these
instructions. If you ignore them, injury or death, or
equipment malfunction can occur, and electromagnetic interference can increase.
•
If you are not a qualified electrician, do not do grounding work.
•
Always ground the drive, the motor and adjoining equipment. This is necessary for the
personnel safety. Proper grounding also reduces electromagnetic emission and
interference.
•
Make sure that the conductivity of the grounding conductors is sufficient. See section
on page
. Obey the local regulations.
•
Connect the power cable shields to protective earth (PE) of the drive to make sure of
personnel safety.
•
Make a 360° grounding of the power and control cable shields at the cable entries to
suppress electromagnetic disturbances.
•
In a multiple-drive installation, connect each drive separately to the protective earth
(PE) busbar of the switch board or the transformer.
Note:
•
You can use power cable shields as grounding conductors only when their conductivity
is sufficient.
•
As the normal touch current of the drive is higher than 3.5 mA AC or 10 mA DC, you
must use a fixed protective earth connection. See standard EN 61800-5-1, 4.3.5.5.2.
Summary of Contents for ACS880-04F
Page 1: ...ABB industrial drives Hardware manual ACS880 04F drive modules ...
Page 4: ......
Page 24: ...24 Introduction to the manual ...
Page 46: ...46 Guidelines for planning the mechanical installation ...
Page 102: ...102 Installation checklist ...
Page 106: ...106 Fault tracing ...
Page 135: ...Technical data 135 Declaration of Conformity ...
Page 136: ...136 Technical data ...
Page 140: ...140 Technical data ...
Page 142: ...142 Dimension drawings Standard configuration IP20 UL Open Type ...
Page 143: ...Dimension drawings 143 Drive module with options E208 and H370 IP20 UL Open Type ...
Page 144: ...144 Dimension drawings Drive module with options 0B051 E208 0H371 IP00 UL Open Type ...
Page 145: ...Dimension drawings 145 Drive module with options 0B051 E208 0H371 C217 IP00 UL Open Type ...
Page 146: ...146 Dimension drawings Drive module with options 0B051 0H371 IP00 UL Open Type ...
Page 147: ...Dimension drawings 147 Mounting plate 3AXD50000038119 ...
Page 148: ...148 Dimension drawings 3AXD50000038119 ...
Page 149: ...Dimension drawings 149 External control unit 3axd50000011687 ...
Page 150: ...150 Dimension drawings ...
Page 164: ...164 Safe torque off function ...