68 Guidelines for planning the electrical installation
Note
: If the fuses for the drive protection are placed at the distribution board and the input
cable is dimensioned according to the nominal input current of the drive given in the rating
table on page
, the fuses will protect also the input cable in short-circuit situations,
restrict drive damage and prevent damage to adjoining equipment in case of a short-circuit
inside the drive. No separate fuses for the input cable protection are needed.
Circuit breakers
The protective characteristics of circuit breakers depend on the type, construction and
settings of the breakers. There are also limitations pertaining to the short-circuit capacity of
the supply network. Your local ABB representative can help you in selecting the breaker
type when the supply network characteristics are known.
You can use the circuit breakers listed below. Other circuit breakers can be used with the
drive if they provide the same electrical characteristics. ABB does not assume any liability
whatsoever for the correct function and protection with circuit breakers not listed below.
Furthermore, if the recommendations given by ABB are not obeyed, the drive can
experience problems that the warranty does not cover.
Note:
Fuses must be used with circuit breakers in the USA.
1)
Maximum allowed rated conditional short-circuit current (IEC 61439-1) of the electrical power network
2)
Contact your local ABB representative
WARNING!
Due to the inherent operating principle and construction of circuit
breakers, independent of the manufacturer, hot ionized gases can escape from
the breaker enclosure in case of a short-circuit. To ensure safe use, pay special
attention to the installation and placement of the breakers. Obey the manufacturer’s
instructions.
Protecting the motor and motor cable in short-circuits
The drive protects the motor cable and motor in a short-circuit situation when the motor
cable is dimensioned according to the nominal current of the drive. No additional
protection devices are needed.
Drive module type
Frame size
ABB molded case circuit breaker (Tmax)
Product ID (Type)
kA
1)
U
N
= 400 V
ACS880-04-725A-3
R11
1SDA062770R1
(T7H 1000 PR231/P LS/I In=1000A 3p F F)
50
ACS880-04-820A-3
R11
1SDA062770R1
(T7H 1000 PR231/P LS/I In=1000A 3p F F)
50
ACS880-04-880A-3
R11
1SDA062770R1
(T7H 1000 PR231/P LS/I In=1000A 3p F F)
50
U
N
= 500 V
ACS880-04-715A-5
R11
1SDA062770R1
(T7H 1000 PR231/P LS/I In=1000A 3p F F)
50
ACS880-04-820A-5
R11
1SDA062770R1
(T7H 1000 PR231/P LS/I In=1000A 3p F F)
50
ACS880-04-880A-5
R11
1SDA062770R1
(T7H 1000 PR231/P LS/I In=1000A 3p F F)
50
3AXD00000588487
Summary of Contents for ACS880-04F
Page 1: ...ABB industrial drives Hardware manual ACS880 04F drive modules ...
Page 4: ......
Page 24: ...24 Introduction to the manual ...
Page 46: ...46 Guidelines for planning the mechanical installation ...
Page 102: ...102 Installation checklist ...
Page 106: ...106 Fault tracing ...
Page 135: ...Technical data 135 Declaration of Conformity ...
Page 136: ...136 Technical data ...
Page 140: ...140 Technical data ...
Page 142: ...142 Dimension drawings Standard configuration IP20 UL Open Type ...
Page 143: ...Dimension drawings 143 Drive module with options E208 and H370 IP20 UL Open Type ...
Page 144: ...144 Dimension drawings Drive module with options 0B051 E208 0H371 IP00 UL Open Type ...
Page 145: ...Dimension drawings 145 Drive module with options 0B051 E208 0H371 C217 IP00 UL Open Type ...
Page 146: ...146 Dimension drawings Drive module with options 0B051 0H371 IP00 UL Open Type ...
Page 147: ...Dimension drawings 147 Mounting plate 3AXD50000038119 ...
Page 148: ...148 Dimension drawings 3AXD50000038119 ...
Page 149: ...Dimension drawings 149 External control unit 3axd50000011687 ...
Page 150: ...150 Dimension drawings ...
Page 164: ...164 Safe torque off function ...