154 Safe torque off function
The function also corresponds to Prevention of unexpected start-up as specified by
EN 1037:1995 + A1:2008 and Uncontrolled stop (stop category 0) as specified in
EN 60204-1:2006 + AC:2010.
Compliance with the European Machinery Directive
See section
Compliance with the European Machinery Directive
on page
Wiring
The following diagrams present examples of Safe torque off wiring for
•
a single drive (page
•
)
•
multiple drives when an external 24V DC power supply is used (page
For information on the specifications of the STO input, see section
on page
Activation switch
In the wiring diagrams below, the activation switch has the designation [K]. This represents
a component such as a manually operated switch, an emergency stop push button switch,
or the contacts of a safety relay or safety PLC.
•
In case a manually operated activation switch is used, the switch must be of a type
that can be locked out to the open position.
•
The contacts of the switch or relay must open/close within 200 ms of each other.
•
An FSO-xx safety functions module can also be used. For more information, see the
FSO-xx module documentation.
Cable types and lengths
We recommend double-shielded twisted-pair cable (see page
).
IEC 61508-1:2010
Functional safety of electrical/electronic/programmable electronic safety-
related systems – Part 1: General requirements
IEC 61508-2:2010
Functional safety of electrical/electronic/programmable electronic safety-
related systems – Part 2: Requirements for
electrical/electronic/programmable electronic safety-related systems
IEC 61511:2016
Functional safety – Safety instrumented systems for the process industry
sector
IEC/EN 61800-5-2:2016
Adjustable speed electrical power drive systems –
Part 5-2: Safety requirements – Functional
IEC 62061:2015
EN 62061:2005
+AC:2010+A1:2013+A2:2015
Safety of machinery – Functional safety of safety-related electrical,
electronic and programmable electronic control systems
EN ISO 13849-1:2015
Safety of machinery – Safety-related parts of control systems – Part 1:
General principles for design
EN ISO 13849-2:2012
Safety of machinery – Safety-related parts of control systems – Part 2:
Validation
Standard
Name
Summary of Contents for ACS880-04F
Page 1: ...ABB industrial drives Hardware manual ACS880 04F drive modules ...
Page 4: ......
Page 24: ...24 Introduction to the manual ...
Page 46: ...46 Guidelines for planning the mechanical installation ...
Page 102: ...102 Installation checklist ...
Page 106: ...106 Fault tracing ...
Page 135: ...Technical data 135 Declaration of Conformity ...
Page 136: ...136 Technical data ...
Page 140: ...140 Technical data ...
Page 142: ...142 Dimension drawings Standard configuration IP20 UL Open Type ...
Page 143: ...Dimension drawings 143 Drive module with options E208 and H370 IP20 UL Open Type ...
Page 144: ...144 Dimension drawings Drive module with options 0B051 E208 0H371 IP00 UL Open Type ...
Page 145: ...Dimension drawings 145 Drive module with options 0B051 E208 0H371 C217 IP00 UL Open Type ...
Page 146: ...146 Dimension drawings Drive module with options 0B051 0H371 IP00 UL Open Type ...
Page 147: ...Dimension drawings 147 Mounting plate 3AXD50000038119 ...
Page 148: ...148 Dimension drawings 3AXD50000038119 ...
Page 149: ...Dimension drawings 149 External control unit 3axd50000011687 ...
Page 150: ...150 Dimension drawings ...
Page 164: ...164 Safe torque off function ...