42 Guidelines for planning the mechanical installation
Note
: When the bottom grille and clear plastic shrouds around the motor cables are
installed, the degree of protection of the drive module from bottom side is IP20.
Planning the electromagnetic compatibility (EMC) of the cabinet
Note the following when you plan the electromagnetic compatibility of the cabinet:
•
Generally, the fewer and smaller the holes in the cabinet, the better the interference
attenuation. The maximum recommended diameter of a hole in galvanic metal contact
in the covering cabinet structure is 100 mm (3.94 in). Pay special attention to the
cooling air inlet and outlet gratings.
•
The best galvanic connection between the steel panels is achieved by welding them
together as no holes are necessary. If welding is not possible, we recommend to leave
the seams between the panels
unpainted
and equipped with special conductive EMC
strips to provide adequate galvanic connection. Usually, reliable strips are made of
flexible silicon mass covered with a metal mesh. The non-tightened touch-contact of
the metal surfaces is not sufficient, so a conductive gasket between the surfaces is
required. The maximum recommended distance between assembly screws is 100 mm
(3.94 in).
•
Construct sufficient high-frequency grounding network in the cabinet to avoid voltage
differences and forming of high-impedance radiator structures. A good high-frequency
grounding is made with short flat copper braids for low inductance. One-point high-
frequency grounding cannot be used due to the long distances inside the cabinet.
•
360° high frequency grounding of the cable shields at the cable lead-throughs
improves the EMC shielding of the cabinet.
The carrying structure on a cable channel
Cabinet side view with a bottom plate
Summary of Contents for ACS880-04F
Page 1: ...ABB industrial drives Hardware manual ACS880 04F drive modules ...
Page 4: ......
Page 24: ...24 Introduction to the manual ...
Page 46: ...46 Guidelines for planning the mechanical installation ...
Page 102: ...102 Installation checklist ...
Page 106: ...106 Fault tracing ...
Page 135: ...Technical data 135 Declaration of Conformity ...
Page 136: ...136 Technical data ...
Page 140: ...140 Technical data ...
Page 142: ...142 Dimension drawings Standard configuration IP20 UL Open Type ...
Page 143: ...Dimension drawings 143 Drive module with options E208 and H370 IP20 UL Open Type ...
Page 144: ...144 Dimension drawings Drive module with options 0B051 E208 0H371 IP00 UL Open Type ...
Page 145: ...Dimension drawings 145 Drive module with options 0B051 E208 0H371 C217 IP00 UL Open Type ...
Page 146: ...146 Dimension drawings Drive module with options 0B051 0H371 IP00 UL Open Type ...
Page 147: ...Dimension drawings 147 Mounting plate 3AXD50000038119 ...
Page 148: ...148 Dimension drawings 3AXD50000038119 ...
Page 149: ...Dimension drawings 149 External control unit 3axd50000011687 ...
Page 150: ...150 Dimension drawings ...
Page 164: ...164 Safe torque off function ...