ACQ550-U1 User’s Manual
301
Technical data
IEC/EN 61800-3 (2004) Definitions
EMC stands for
E
lectro
m
agnetic
C
ompatibility. It is the ability of electrical/electronic
equipment to operate without problems within an electromagnetic environment.
Likewise, the equipment must not disturb or interfere with any other product or
system within its locality.
First environment
includes establishments connected to a low-voltage network which
supplies buildings used for domestic purposes.
Second environment
includes establishments connected to a network not directly
supplying domestic premises.
Drive of category C2:
drive of rated voltage less than 1000 V and intended to be
installed and commissioned only by a professional when used in the first
environment.
Note:
A professional is a person or organisation having necessary skills in installing
and/or commissioning power drive systems, including their EMC aspects.
Category C2 has the same EMC emission limits as the earlier class first environment
restricted distribution. EMC standard IEC/EN 61800-3 does not any more restrict the
distribution of the drive, but the using, installation and commissioning are defined.
Drive of category C3:
drive of rated voltage less than 1000 V, intended for use in the
second environment and not intended for use in the first environment.
Category C3 has the same EMC emission limits as the earlier class second
environment unrestricted distribution.
Compliance with the IEC/EN 61800-3 (2004)
The immunity performance of the drive complies with the demands of IEC/
EN 61800-3, category C2 (see page
for IEC/EN 61800-3 definitions). The
emission limits of IEC/EN 61800-3 are complied with the provisions described below.
First environment (drives of category C2)
1. The internal EMC filter is connected.
2. The motor and control cables are selected as specified in this manual.
3. The drive is installed according to the instructions given in this manual.
4. The motor cable length does not exceed the allowed maximum length specified in
section
Motor cable length for 400 V drives
on page
for the frame size and
switching frequency in use.
WARNING!
In a domestic environment, this product may cause radio inference, in
which case supplementary mitigation measures may be required.
Second environment (drives of category C3)
1. The internal EMC filter is connected.
2. The motor and control cables are selected as specified in this manual.
3. The drive is installed according to the instructions given in this manual.
Summary of Contents for ACQ550-U1-011A-6
Page 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 U1 User s Manual Table of contents ...
Page 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Page 56: ...56 ACQ550 U1 User s Manual Control panel ...
Page 68: ...68 ACQ550 U1 User s Manual Application macros ...
Page 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Page 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Page 314: ...314 ACQ550 U1 User s Manual Index ...