ACQ550-U1 User’s Manual
165
8104
REFERENCE STEP 2
Sets a percentage value that is added to the process reference.
• Applies only when at least two auxiliary (constant speed) motors are running.
• See parameter 8103
REFERENCE
STEP
1.
8105
REFERENCE STEP 3
Sets a percentage value that is added to the process reference.
• Applies only when at least three auxiliary (constant speed) motors are running.
• See parameter 8103
REFERENCE
STEP
1.
8109
START FREQ 1
Sets the frequency limit used to start the first auxiliary motor. The first auxiliary motor starts if:
• No auxiliary motors are running.
• ACQ550 output frequency exceeds the limit:
8109 + 1 Hz.
• Output frequency stays above a relaxed limit
(8109 - 1 Hz) for at least the time: 8115
AUX
MOT
START
D
.
After the first auxiliary motor starts:
• Output frequency decreases by the value =
(8109
START
FREQ
1) - (8112
LOW
FREQ
1).
• In effect, the output of the speed regulated motor drops to
compensate for the input from the auxiliary motor.
See the figure, where:
• A = (8109
START
FREQ
1) - (8112
LOW
FREQ
1)
• B = Output frequency increase during the start delay.
• C = Diagram showing auxiliary motor’s run status as frequency
increases (1 = On).
Note:
8109
START
FREQ
1 value must be between:
• 8112
LOW
FREQ
1
• (2008
MAXIMUM
FREQ
) -1.
8110
START FREQ 2
Sets the frequency limit used to start the second auxiliary motor.
• See 8109
START
FREQ
1 for a complete description of the operation.
The second auxiliary motor starts if:
• One auxiliary motor is running.
• ACQ550 output frequency exceeds the limit: 8110 + 1.
• Output frequency stays above the relaxed limit (8110 - 1 Hz) for at least the time: 8115
AUX
MOT
START
D
.
8111
START FREQ 3
Sets the frequency limit used to start the third auxiliary motor.
• See 8109
START
FREQ
1 for a complete description of the operation.
The third auxiliary motor starts if:
• Two auxiliary motors are running.
• ACQ550 output frequency exceeds the limit: 8111 + 1 Hz.
• Output frequency stays above the relaxed limit (8111 - 1 Hz) for at least the time: 8115
AUX
MOT
START
D
.
Code Description
P 8115
(P 8109)+1
P 8112
A
B
1
0
C
P 8109
A
t
t
f
(Hz)
f
MIN
f
MAX
Summary of Contents for ACQ550-U1-011A-6
Page 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 U1 User s Manual Table of contents ...
Page 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Page 56: ...56 ACQ550 U1 User s Manual Control panel ...
Page 68: ...68 ACQ550 U1 User s Manual Application macros ...
Page 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Page 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Page 314: ...314 ACQ550 U1 User s Manual Index ...