![ABB ACQ550-U1-011A-6 User Manual Download Page 242](http://html.mh-extra.com/html/abb/acq550-u1-011a-6/acq550-u1-011a-6_user-manual_3261242.webp)
242
ACQ550-U1 User’s Manual
Fieldbus adapter
4
OFF_2_STA
1
OFF
2 inactive
0
OF
F
2
ACTIVE
5
OFF_3_STA
1
OFF
3 inactive
0
OF
F
3
ACTIVE
6
SWC_ON_INHIB
1
SWITCH
-
ON
INHIBIT
ACTIVE
0
SWITCH
-
ON
INHIBIT
NOT
ACTIVE
7
ALARM
1
Alarm (See section
on page
for details
on alarms.)
0
No alarm
8
AT_SETPOINT
1
OPERATING
.
Actual value equals (within tolerance limits)
the reference value.
0
Actual value is outside tolerance limits (not equal to
reference value).
9
REMOTE
1
Drive control location:
REMOTE
(
EXT
1 or
EXT
2)
0
Drive control location:
LOCAL
10
ABOVE_LIMIT
1
Supervised parameter’s value > supervision high limit.
Bit remains “1” until supervised parameter’s value <
supervision low limit.
See
.
0
Supervised parameter’s value < supervision low limit.
Bit remains “0” until supervised parameter’s value >
supervision high limit.
See
.
11
EXT CTRL LOC
1
External control location 2 (
EXT
2) selected
0
External control location 1 (
EXT
1) selected
12
EXT RUN ENABLE
1
External Run Enable signal received
0
No External Run Enable signal received
13… 15 Unused
ABB Drives profile (FBA)
STATUS
WORD
Bit
Name
Value
Description
(Correspond to states/boxes in the state diagram)
Summary of Contents for ACQ550-U1-011A-6
Page 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 U1 User s Manual Table of contents ...
Page 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Page 56: ...56 ACQ550 U1 User s Manual Control panel ...
Page 68: ...68 ACQ550 U1 User s Manual Application macros ...
Page 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Page 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Page 314: ...314 ACQ550 U1 User s Manual Index ...