258
ACQ550-U1 User’s Manual
Diagnostics
The ACQ Control Panel provides additional information about the fault history. See
section
on page
for more information.
To clear the fault history (all of the
parameters):
1. Using the control panel in the Parameters mode, select parameter 0401.
2. Press EDIT.
3. Press UP and DOWN at the same time.
4. Press SAVE.
Correcting alarms
The recommended corrective action for alarms is:
•
Determine if the alarm requires any corrective action (action is not always
required).
•
Use the table in section
below to find and address the root cause of
the problem.
Alarm listing
The following table lists the alarms by code number and describes each.
Alarm
code
Display
Description
2001
OVERCURRENT
Current limiting controller is active. Check for and correct:
• Excessive motor load.
• Insufficient acceleration time (parameters 2202
ACCELER
TIME
1 and
2205
ACCELER
TIME
2).
• Faulty motor, motor cables or connections.
2002
OVERVOLTAGE
Overvoltage controller is active. Check for and correct:
• Static or transient overvoltages in the input power supply.
• Insufficient deceleration time (parameters 2203
DECELER
TIME
1 and
2206
DECELER
TIME
2).
2003
UNDERVOLTAGE
Undervoltage controller is active. Check for and correct:
• Undervoltage on mains.
2004
DIR
LOCK
The change in direction being attempted is not allowed. Either:
• Do not attempt to change the direction of motor rotation, or
• Change parameter 1003
DIRECTION
to allow direction change (if
reverse operation is safe).
2005
IO
COMM
Fieldbus communication has timed out. Check for and correct:
• Fault setup (3018
COMM
FAULT
FUNC
and 3019
COMM
FAULT
TIME
).
• Communication settings (
as appropriate).
• Poor connections and/or noise on line.
2006
AI
1
LOSS
Analog input 1 is lost, or value is less than the minimum setting.
Check:
• Input source and connections.
• Parameter that sets the minimum (3021).
• Parameter that sets the alarm/fault operation (3001),
Summary of Contents for ACQ550-U1-011A-6
Page 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 U1 User s Manual Table of contents ...
Page 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Page 56: ...56 ACQ550 U1 User s Manual Control panel ...
Page 68: ...68 ACQ550 U1 User s Manual Application macros ...
Page 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Page 266: ...266 ACQ550 U1 User s Manual Maintenance ...