ACQ550-U1 User’s Manual
157
Group 51: EXT COMM MODULE
This group defines set-up variables for a fieldbus adapter (FBA) communication
module. For more information on these parameters, refer to the user’s manual
supplied with the FBA module.
Code Description
5101
FBA TYPE
Displays the type of the connected fieldbus adapter module.
0 =
NOT
DEFINED
– Module not found, or not properly connected, or parameter 9802 is not set to 4 (
EXT
FBA
).
1 =
PROFIBUS
-
DP
32 =
CAN
open
37 =
DEVICENET
101 =
CONTROLNET
128 =
ETHERNET
132 =
PROFINET
135 = Ether
CAT
136 = EPL – Ethernet POWERLINK
144 = CC-Link
5102
…
5126
FB PAR 2…FB PAR 26
Refer to communication module documentation for more information on these parameters.
5127
FBA PAR REFRESH
Validates any changed fieldbus parameter settings.
0 =
DONE
– Refreshing done.
1 =
REFRESH
– Refreshing.
• After refreshing, the value reverts automatically to
DONE
.
5128
FILE CPI FW REV
Displays the CPI firmware revision of the drive’s fieldbus adapter configuration file. Format is xyz where:
• x = major revision number
• y = minor revision number
• z = correction number
Example:
107 = revision 1.07
5129
FILE CONFIG ID
Displays the revision of the drive’s fieldbus adapter module’s configuration file identification.
• File configuration information is drive application program-dependent.
5130
FILE CONFIG REV
Contains the revision of the drive’s fieldbus adapter module configuration file.
Example:
1 = revision 1
5131
FBA STATUS
Contains the status of the adapter module.
0 =
IDLE
– Adapter not configured.
1 =
EXECUT
INIT
– Adapter is initializing.
2 =
TIME
OUT
– A timeout has occurred in the communication between the adapter and the drive.
3 =
CONFIG
ERROR
– Adapter configuration error.
• The revision code of the adapter’s CPI firmware revision is older than required CPI firmware version defined in
the drive’s configuration file (parameter 5132 < 5128).
4 =
OFF
-
LINE
– Adapter is off-line.
5 =
ON
-
LINE
– Adapter is on-line.
6 =
RESET
– Adapter is performing a hardware reset.
5132
FBA CPI FW REV
Contains the revision of the module’s CPI program. Format is xyz where:
• x = major revision number
• y = minor revision number
• z = correction number
Example:
107 = revision 1.07
5133
FBA APPL FW REV
Contains the revision of the module’s application program. Format is xyz (see parameter 5132).
Summary of Contents for ACQ550-U1-011A-6
Page 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 U1 User s Manual Table of contents ...
Page 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Page 56: ...56 ACQ550 U1 User s Manual Control panel ...
Page 68: ...68 ACQ550 U1 User s Manual Application macros ...
Page 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Page 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Page 314: ...314 ACQ550 U1 User s Manual Index ...