82
ACQ550-U1 User’s Manual
Parameters
6433
AL
2
RANGE
90
TO
0.0…100.0%
0.1%
-
Group 81: PFC CONTROL
8103
REFERENCE
STEP
1
0.0…100.0%
0.1%
0.0%
8104
REFERENCE
STEP
2
0.0…100.0%
0.1%
0.0%
8105
REFERENCE
STEP
3
0.0…100.0%
0.1%
0.0%
8109
START
FREQ
1
0.0…500.0 Hz
0.1 Hz
-U1: 60.0 Hz
8110
START
FREQ
2
0.0…500.0 Hz
0.1 Hz
-U1: 60.0 Hz
8111
START
FREQ
3
0.0…500.0 Hz
0.1 Hz
-U1: 60.0 Hz
8112
LOW
FREQ
1
0.0…500.0 Hz
0.1 Hz
-U1: 30.0 Hz
8113
LOW
FREQ
2
0.0…500.0 Hz
0.1 Hz
-U1: 30.0 Hz
8114
LOW
FREQ
3
0.0…500.0 Hz
0.1 Hz
-U1: 30.0 Hz
8115
AUX
MOT
START
D
0.0…3600.0 s
0.1 s
5.0 s
8116
AUX
MOT
STOP
D
0.0…3600.0 s
0.1 s
3.0 s
8117
NR
OF
AUX
MOT
0…4 1
1
8118
AUTOCHNG
INTERV
-0.1 =
TEST
MODE
, 0.0 =
NOT
SEL
,
0.1…336.0 h
0.1 h
0.0 h (
NOT SEL
)
8119
AUTOCHNG
LEVEL
0.0…100.0%
0.1%
50.0%
8120
INTERLOCKS
0…6
1
4 (
DI
4)
8121
REG
BYPASS
CTRL
0 =
NO
, 1 =
YES
1
0 (
NO
)
8122
PFC
START
DELAY
0.00…10.00 s
0.01 s
0.50 s
8123
PFC
ENABLE
0 =
NOT
SEL
, 1 =
ACTIVE
1
0 (
NOT SEL
)
8124
ACC
IN
AUX
STOP
0.0 =
NOT
SEL
, 0.1…1800.0 s
0.1 s
0.0 s (
NOT
SEL
)
8125
DEC
IN
AUX
START
0.0 =
NOT
SEL
, 0.1…1800.0 s
0.1 s
0.0 s (
NOT
SEL
)
8126
TMED
AUTOCHNG
0…4
1
0 (
NOT SEL
)
8127
MOTORS
1…7
1
2
8128
AUX
START
ORDER
1 =
EVEN
RUNTIME
, 2 =
RELAY
ORDER
1
1 (
EVEN
RUNTIME
)
Group 98: OPTIONS
9802
COMM
PROT
SEL
0 =
NOT
SEL
, 1 =
STD
MODBUS
,
4 =
EXT FBA
, 5 =
BACNET
1
0 (
NOT SEL
)
Code
Name
Range
Resolution
Default
User
S
Summary of Contents for ACQ550-U1-011A-6
Page 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 U1 User s Manual Table of contents ...
Page 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Page 56: ...56 ACQ550 U1 User s Manual Control panel ...
Page 68: ...68 ACQ550 U1 User s Manual Application macros ...
Page 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Page 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Page 314: ...314 ACQ550 U1 User s Manual Index ...