212
ACQ550-U1 User’s Manual
Embedded fieldbus
State diagram
ABB Drives profile
To illustrate the operation of the state diagram, the following example (
ABB
DRV
LIM
implementation of the ABB Drives profile) uses the control word to start the drive:
•
First, the requirements for using the
CONTROL
WORD
must be met. See above.
•
When the power is first connected, the state of the drive is not ready to switch on.
See dotted lined path (
) in the state diagram below.
•
Use the
CONTROL
WORD
to step through the state machine states until the
OPERATING
state is reached, meaning that the drive is running and follows the
given reference. See the table below.
Step
CONTROL
WORD
Value
Description
1
CW = 0000 0000 0000 0110
This CW value changes the drive state to
READY
TO
SWITCH
ON
.
2
Wait at least 100 ms before proceeding.
3
CW = 0000 0000 0000 0111
This CW value changes the drive state to
READY
TO
OPERATE
.
4
CW = 0000 0000 0000 1111
This CW value changes the drive state to
OPERATION
ENABLED
.
The drive starts, but will not accelerate.
5
CW = 0000 0000 0010 1111
This CW value releases the ramp function generator (RFG)
output and changes the drive state to
RFG
:
ACCELERATOR
ENABLED
.
6
CW = 0000 0000 0110 1111
This CW value releases the ramp function generator (RFG)
output and changes the drive state to
OPERATING
. The drive
accelerates to the given reference and follows the reference.
bit 0
bit 15
Summary of Contents for ACQ550-U1-011A-6
Page 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 U1 User s Manual Table of contents ...
Page 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Page 56: ...56 ACQ550 U1 User s Manual Control panel ...
Page 68: ...68 ACQ550 U1 User s Manual Application macros ...
Page 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Page 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Page 314: ...314 ACQ550 U1 User s Manual Index ...