Processor Module
PM59x-ETH
PM59x-
ARCNET
PM59x-ETH
PM59x-2ETH
Binary
Min. 0.002
µ
s
Min. 0.002
µ
s
Min. 0.002
µ
s
Word
Min. 0.004
µ
s
Min. 0.004
µ
s
Min. 0.004
µ
s
Floating point
Min. 0.004
µ
s
Min. 0.004
µ
s
Min. 0.004
µ
s
Max. number of central inputs and outputs
(up to 7 exp. modules):
1
)
Digital inputs
224
224
224
Digital outputs
224
224
224
Analog inputs
112
112
112
Analog outputs
112
112
112
Max. number of central inputs and outputs
(10 exp. modules):
Digital inputs
320
320
320
Digital outputs
320
320
320
Analog inputs
160
160
160
Analog outputs
160
160
160
Number of decentralized inputs and out-
puts
Depends on the fieldbus used
(as an info on the CS31 bus: up to 31 stations with
up to 120 DI / 120 DO each)
Data backup
Battery
Data buffering time at 25
°
C
Typ. 3 years without power supply
Battery low indication
Warning issued about 2 weeks before the state of
charge becomes critical
Real-time clock:
With battery back-up
x
x
x
Accuracy
Typ.
±
2 s / day
at 25
°
C
Typ.
±
2 s / day
at 25
°
C
Typ.
±
2 s / day
at 25
°
C
Program execution:
Cyclic
x
x
x
Time-controlled
x
x
x
Multitasking
x
x
x
Password protection of user program
x
x
x
Serial interface COM1:
Physical link
Configurable for RS-232 or RS-485 (from 0.3 to
187.5 kB/s) pluggable terminal block, spring con-
nection for programming, as Modbus (master/
slave), as serial ASCII communication, as CS31
master
Connection
Usage
Serial interface COM2 (not for
PM5xy-2ETH models):
Physical link
Configurable for RS-232 or RS-485 (from 0.3 to
187.5 kB/s) D-sub for programming, as Modbus
(master/slave), as serial ASCII communication
Connection
Usage
Integrated communication module:
Device Specifications
Processor Modules > AC500 (Standard)
2019/04/17
3ADR010121, 13, en_US
76