Technical Data of the Analog Inputs
Parameter
Value
Number of channels per module
2 voltage inputs
Distribution of channels into groups
1 group for 2 channels
Galvanic isolation
None
Power Supply Voltage
Via the L+ and the M terminal of the pro-
cessor-module power supply
Resolution
Voltage 0 VDC...10 VDC: 10 bits
Connection of the signals AI0 and AI1
Terminals 8 and 9
Input type
Unipolar
Data word format
Unipolar, full-scale range
0 to 27648
Indication of the input signals
No
Channel input resistance
Voltage: > 100 k
W
Accuracy
Typical (25 °C)
±
1 %
Worst case (at 0 °C...60 °C or EMC distur-
bances)
±
2.5 % of full-scale
Time constant of the input filter
Typ. 1 ms
Relationship between input signal and hex
code
Chapter 1.2.1.3.9 “Measuring Ranges”
Analog to digital conversion time
Typ. 6.2 ms
Unused inputs
Can be left open and should be configured
as "unused"
Overvoltage protection
Yes, up to 30 VDC
Max. cable length
Conductor cross section > 0.14 mm
²
Unshielded wire
On request
Shielded wire
100 m
Technical Data of the Analog Output
Parameter
Value
Number of channels per module
1 configurable voltage or current outputs
Distribution of channels into groups
1 group for 1 channel
Electrical isolation
None
Connection of the signal AOU
Terminal 11
Connection of the signal AOI
Terminal 10
Power supply voltage
Via the L+ and the M terminal of the pro-
cessor module power supply
Output type
Unipolar (voltage and current)
Resolution
10 bits
Indication of the output signals
Yes, one LED per channel
Output Resistance (load) as current output
0
W
...500
W
Device Specifications
Processor Modules > AC500-eCo
2019/04/17
3ADR010121, 13, en_US
64