E1...E4
d1
d2
d3
d4
Identifier
000...063
AC500-
Display
<− Display in
Class
Comp
Dev
Mod
Ch
Err
PS501
PLC
Browser
Class
Inter-
face
Device
Module
Channel
Error-
Identifier
Error message
Remedy
3
8
255
3
0
26
Invalid configuration of
onboard I/O module, e.
g. 2 input channels are
configured as fast
counter and interrupt
input at the same time.
Correct
PLC con-
figuration
Warnings
4
8
1
2
1
2
Invalid configuration
value for PWM channel.
Frequency / cycletime
for the PWM channel of
the 8DI+6DO and 8DI
+6DO+2AI+1AO
module are common
and if both channel are
configured for PWM,
the frequency of the
second channel must
be set to 0.
Correct
frequency
4
8
1
2
0..1
4
PWM channel fre-
quency or cycle time
too high
Correct
frequency
or cycle
time
4
8
1
2
0..1
7
PWM channel fre-
quency or cycle time
too low
Correct
frequency
or cycle
time
4
8
1
2
0
52
Frequency on interrupt
input pin too high and
interrupt events are
missed
Correct
frequency
4
8
4
2
0..1
48
Analog input value too
high
Correct
value
4
8
5
2
0
48
Analog output value too
high
Correct
value
4
8
255
2
0
26
PLC was put into RUN
state, although a config-
uration error is present,
because parameter
Run on config fault is
set to YES
Correct
PLC con-
figuration
4
8
255
0
0
43
Unspecified or internal
error occured
Replace
processor
module
Device Specifications
Processor Modules > AC500-eCo
2019/04/17
3ADR010121, 13, en_US
58