Parameter
Value
Indication of the output signals
1 yellow LED per channel; the LED is on
when the output signal is high (signal 1) and
the module is powered through the I/O bus
Way of operation
Non-latching type
Output delay
0 to 1
Typ. 10 ms
1 to 0
Typ. 10 ms
Rated protection fuse
On request
Output current
Rated current per channel (max.)
2.0 A (24 VDC / 24 VAC / 48 VAC /
120 VAC / 240 VAC, only resistive loads)
2.0 A (24 VAC / 48 VAC / 120 VAC, only pilot
duty)
1.5 A (240 VAC, only pilot duty)
Rated current per group (max.)
6 A
Rated current (all channels together, max.)
12 A
Lamp load (max.)
200 W (230 VAC), 30 W (24 VDC)
Demagnetization when inductive loads are
switched off
A free-wheeling diode must be circuited in
parallel to the inductive load
Spark suppression with inductive AC loads
Must be performed externally according to
driven load specification
Switching frequencies
With resistive loads
Max. 1 Hz
With inductive loads
Not possible
With lamp loads
Max. 1 Hz
Short-circuit-proof / Overload-proof
No, should be provided by an external fuse
or circuit breaker
Rated protection fuse (for each channel)
5 A fast
Overload message
No
Output current limitation
No
Resistance to feedback against 24 VDC
No
Connection of 2 outputs in parallel
Not possible
Life time of relay contacts (cycles)
100.000 at rated load
Max. cable length
Shielded
500 m
Unshielded
150 m
Technical Data of the PWM Outputs
Parameter
Value
Used outputs for PWM
DO2 and DO3
Output frequency
125 Hz 20 kHz
Device Specifications
Processor Modules > AC500-eCo
2019/04/17
3ADR010121, 13, en_US
63