1.2.2.1.2 Assortment
Module
Program
and Data
Memory
Cycle Time
for 1 Instruc-
tion
Network Interface
Other Inter-
faces
Suitable
Terminal Base
Ethernet
ARCNET
PM572
128 kB
Binary: min.
0.06
µ
s
Word: min.
0.09
µ
s
Floating point:
min. 0.70
µ
s
-
-
3
)
TB5x1-ETH
PM573-ETH 512 kB
Onboard
Ethernet
-
3
)
TB5x1-ETH
(1SAP11x100R0
270 only)
PM582
512 kB
Binary: min.
0.05
µ
s
Word: min.
0.06
µ
s
Floating point:
min. 0.50
µ
s
-
-
3
)
TB5x1-ETH
PM583-ETH 1 MB
Onboard
Ethernet
-
3
)
TB5x1-ETH
(1SAP11x100R0
270 only)
PM585-ETH 1 MB
3
)
PM590-ETH
(
1
)
2 MB
Binary: min.
0.002
µ
s
Word: min.
0.004
µ
s
Floating point:
min. 0.004
µ
s
Integrated com-
munication
module
-
3
)
TB5x1-ETH
PM590-
ARCNET
(R0261)
2 MB
-
-
Integrated
communication
module
3
)
TB5x1-ARCNET
PM591-ETH 4 MB
-
Integrated com-
munication
module
-
3
)
TB5x1-ETH
PM591-ETH 4 MB
-
Onboard
Ethernet
-
3
)
TB5x1-ETH
(1SAP11x100R0
270 only)
PM591-2ET
H
4 MB
-
2x Onboard
Ethernet
-
2
)
TB5x3-2ETH
PM592-ETH 4 MB
Onboard
Ethernet
-
3
)
TB5x1-ETH
(1SAP11x100R0
270 only)
Remarks:
1
): The processor modules PM59x-ETH can only be used with terminal bases with product index
C6 or higher. Otherwise, they should be updated to that index.
2
): Serial interface COM1, Communication Interface Module, I/O bus
3
): Serial interface COM1, Serial interface COM1, Communication Interface Module, FieldBus-
Plug (FBP), I/O bus
Processor modules PM57x-ETH, PM58x-ETH and PM59x-ETH with ordering
No. 1SAPxxxxxxR0271 can only be used with terminal bases with ordering No.
1SAPxxxxxxR0270.
Processor modules PM5xx-2ETH can only be used with TB5x3-2ETH terminal
bases.
Device Specifications
Processor Modules > AC500 (Standard)
2019/04/17
3ADR010121, 13, en_US