CAUTION!
Risk of damaging the processor module!
–
Never short-circuit or overload the outputs.
–
Never connect inductive loads without an external suppression against
voltage peaks due to inductive kickback.
–
Never connect voltages > 240 V. All outputs must be fed from the same
phase.
–
Use an external 5 A fast protection fuse for the outputs.
1.2.1.2.4 Internal Data Exchange
Parameter
Value
Digital inputs (bytes)
1
Digital outputs (bytes)
1
1.2.1.2.5 I/O Configuration
The configuration data of the onboard I/Os is stored in the processor podule PM55x.
1.2.1.2.6 Parameterization
For information about parameterization, refer to the description for onboard I/Os for processor
1.2.1.2.7 Diagnosis
E1...E
4
d1
d2
d3
d4
Identifier
000...063
AC500-Display
<− Display in
Class Comp Dev
Mod
Ch
Err
PS501 PLC Browser
Class Inter-
face
Device Module Channel Error-
Identifier
Error message
Remedy
Errors for Onboard I/O
Light errors
3
8
255
2
0
3
MaxWaitRun for onboard I/O
module has expired, when PLC
is put into RUN state
Reboot and try it
again. If the error
still exists, replace
processor module
for testing
3
8
255
3
0
26
Invalid configuration of onboard
I/O module, e. g. 2 input chan-
nels are configured as fast
counter and interrupt input at
the same time.
Correct PLC con-
figuration
Warnings