![background image](http://html.mh-extra.com/html/abb/ac-800m/ac-800m_configuration_2904153.webp)
Section 4 Configuration
Configuring S200 I/O Modules
9ARD000014-600 A
153
The Hardware Editor contains four tabs — Settings, Connections, Status and Unit
Status. The parameters for configuring the S200 I/O Modules are found in the
Settings
tab. Configure the parameters according to the description of parameters
given in
These parameters are common for all the S200 I/O Modules.
Apart from these there are specific settings to be done for 200-IP2 and 200-IP4 I/O
Modules.
Table 26. Parameters on S200 IO modules
Parameter
Default
Value
Type
Unit
Min
Max
Description
Consequence
Connection
O2TRPI
500
dint
ms
10
1000
Requested Packet
Interval for O->T
packets.
Connection
with the IO
module is
re-established
Connection
T2ORPI
500
dint
ms
10
1000
Requested Packet
Interval for T>O
packets.
Connection
with the IO
module is
re-established
Connection
Timeout
Multiplier
4
dint
-
0
7
Specifies the multiplier
applied to RPI to obtain
the connection time-out
value used for
establishing implicit
messaging connection.
Refer
for
connection time-out
multiplier
Connection
with the IO
module is
re-established
Summary of Contents for AC 800M
Page 2: ......
Page 3: ...AC 800M EtherNet IP DeviceNet Configuration System Version 6 0 ...
Page 10: ...Table of Contents 10 9ARD000014 600 A ...
Page 18: ...Released User Manuals and Release Notes About This User Manual 18 9ARD000014 600 A ...
Page 22: ...Figure 1 System configuration Device Import Wizard Section 1 Introduction 22 9ARD000014 600 A ...
Page 26: ...Linear Network Section 1 Introduction 26 9ARD000014 600 A ...
Page 46: ...Hot Swap of EtherNet IP Device Section 2 Functional Description 46 9ARD000014 600 A ...
Page 68: ...Figure 22 Enum Values File Section 3 Device Import Wizard 68 9ARD000014 600 A ...
Page 71: ...Section 3 Device Import Wizard File 9ARD000014 600 A 71 Figure 25 EDS Range selection ...
Page 222: ...Auxiliary RS 232 9 Pin D Subminiature Section 8 Hardware Connections 222 9ARD000014 600 A ...
Page 259: ......