Appendix B Troubleshooting CI873 Log Entries
Connection Error
9ARD000014-600 A
251
25
No more consumer
resources available
in the producing
object
All the connections to the particular
tag is consumed, and the device will
not accept any more connections to
the tag.
EtherNet/IP
26
Producing Symbol
does not exist
Check if the Tag configured in
control builder is defined in AB PLC
EtherNet/IP
27
The object cannot
perform the
requested service in
its current
mode/state
The device is in a state where it can
not accept any connections. Contact
the device vendor to resolve it.
EtherNet/IP/DeviceNet
Table 42. Connection Errors (Continued)
Sl
No
Message in CI873 Log
Description
Applicability based on
device classification
Summary of Contents for AC 800M
Page 2: ......
Page 3: ...AC 800M EtherNet IP DeviceNet Configuration System Version 6 0 ...
Page 10: ...Table of Contents 10 9ARD000014 600 A ...
Page 18: ...Released User Manuals and Release Notes About This User Manual 18 9ARD000014 600 A ...
Page 22: ...Figure 1 System configuration Device Import Wizard Section 1 Introduction 22 9ARD000014 600 A ...
Page 26: ...Linear Network Section 1 Introduction 26 9ARD000014 600 A ...
Page 46: ...Hot Swap of EtherNet IP Device Section 2 Functional Description 46 9ARD000014 600 A ...
Page 68: ...Figure 22 Enum Values File Section 3 Device Import Wizard 68 9ARD000014 600 A ...
Page 71: ...Section 3 Device Import Wizard File 9ARD000014 600 A 71 Figure 25 EDS Range selection ...
Page 222: ...Auxiliary RS 232 9 Pin D Subminiature Section 8 Hardware Connections 222 9ARD000014 600 A ...
Page 259: ......