The EDS file of some device may have a lot of configuration parameters and
connections. In rare scenarios this would exceed the maximum configuration size
per device in control builder of 65535 bytes. If this happens, a compilation error
would be displayed when the user tries to download such a hardware type to the
controller and the download would be aborted.
User would then need to re-import the EDS file of such a device and delete some
parameters/ connection that are not required so as to bring the configuration size
of the device to acceptable limits.
Guidelines for Re-import and Re-configuration
Section 5 Run-Time Operation
168
9ARD000014-600 A
Guidelines for Re-import and Re-configuration
This section describes the guidelines to be followed during re-import and re-
configuration.
Re-import
There is a possibility of I/O modules duplication within the same hardware library
during re-import.
Consider a modular import scenario in which certain I/O modules are selected to be
imported under the adapter, the hardware types for all the I/O modules are created in
the hardware library.
So all the I/O modules imported are available to be inserted in the hardware tree
under the adapter.
1.
Considering a modular re-import scenario, where, certain I/O modules are
de-selected and only a subset of the modules are imported, which are currently
available under the adapter. These de-selected modules still appears under the
hardware library as they have not been physically deleted from the hardware
library.
However de-selected I/O modules cannot be added in the hardware tree under
the adapter. Hence, only the I/O modules being included or selected in the most
recent import of the adapter will be available for configuration under the
adapter.
Summary of Contents for AC 800M
Page 2: ......
Page 3: ...AC 800M EtherNet IP DeviceNet Configuration System Version 6 0 ...
Page 10: ...Table of Contents 10 9ARD000014 600 A ...
Page 18: ...Released User Manuals and Release Notes About This User Manual 18 9ARD000014 600 A ...
Page 22: ...Figure 1 System configuration Device Import Wizard Section 1 Introduction 22 9ARD000014 600 A ...
Page 26: ...Linear Network Section 1 Introduction 26 9ARD000014 600 A ...
Page 46: ...Hot Swap of EtherNet IP Device Section 2 Functional Description 46 9ARD000014 600 A ...
Page 68: ...Figure 22 Enum Values File Section 3 Device Import Wizard 68 9ARD000014 600 A ...
Page 71: ...Section 3 Device Import Wizard File 9ARD000014 600 A 71 Figure 25 EDS Range selection ...
Page 222: ...Auxiliary RS 232 9 Pin D Subminiature Section 8 Hardware Connections 222 9ARD000014 600 A ...
Page 259: ......