Section 3 Device Import Wizard
I/O Settings
9ARD000014-600 A
81
•
Input Only
- A specific implementation may limit the number of input only
connections it accepts. In addition, the target may accept listen only
connections that use the same multicast T=>O data.
•
Listen Only
- A target may accept multiple listen only connections which
specify the same T=>O path. Devices that wish to listen to multicast data
without providing configuration may use this application type. Is the last
connection on which a listen only connection depends is closed or times out,
the target device shall stop sending the T=>O data which will result in the
listen only connection being timed our by the originator device.
•
Redundant Owner
- The redundant owner connection shall allow multiple
separate originator applications to each establish an independent, identical
connection to the transport of a target application.The target transport shall in
turn send events to the target application so that the redundant owner
connection appears as a single, exclusive owner connection to the target
application.
The CI873 does not support Redundant owner connections for EtherNet/IP
devices.
To create I/O channels for an EtherNet/IP device (Modular and non-modular), refer
I/O Setting and I/O Channel Creation
Allen Bradley Logix 5000 Series PLCs
shows the
I/O Settings
window for Allen Bradley Control Logix PLC
unit. The Class 1 and Class 3 connections can be set in the
I/O Settings
window.
Under each product name/catalog number in the tree view, the connections listed are
— Class 1 Connections and Class 3 Connections.
shows
the Class 1 and Class 3 connection respectively.
Tag based Class 1 connection information should be available in EDS file of the
Logix 5000 Controllers for communication with CI873.
Summary of Contents for AC 800M
Page 2: ......
Page 3: ...AC 800M EtherNet IP DeviceNet Configuration System Version 6 0 ...
Page 10: ...Table of Contents 10 9ARD000014 600 A ...
Page 18: ...Released User Manuals and Release Notes About This User Manual 18 9ARD000014 600 A ...
Page 22: ...Figure 1 System configuration Device Import Wizard Section 1 Introduction 22 9ARD000014 600 A ...
Page 26: ...Linear Network Section 1 Introduction 26 9ARD000014 600 A ...
Page 46: ...Hot Swap of EtherNet IP Device Section 2 Functional Description 46 9ARD000014 600 A ...
Page 68: ...Figure 22 Enum Values File Section 3 Device Import Wizard 68 9ARD000014 600 A ...
Page 71: ...Section 3 Device Import Wizard File 9ARD000014 600 A 71 Figure 25 EDS Range selection ...
Page 222: ...Auxiliary RS 232 9 Pin D Subminiature Section 8 Hardware Connections 222 9ARD000014 600 A ...
Page 259: ......