![ABB AC 800M Configuration Download Page 228](http://html.mh-extra.com/html/abb/ac-800m/ac-800m_configuration_2904228.webp)
Appendix A Troubleshooting EDS File
228
9ARD000014-600 A
15
<EDS file name>
doesn't have any
connection names.
Import cannot
proceed further!
The IO Info section
is not present in
DeviceNet EDS file
or the Connection
name in IO Info
Section required in
EDS file is missing
or fields available as
not as per CIP
specification
DeviceNet
Import will abort.
Contact the vendor to
get device EDS files
with all the mandatory
fields.
16
Invalid device
connections. Please
use correct EDS
file and try again!
The connection
manager section is
not found in EDS
file
EtherNet/IP
Import will abort.
Contact the vendor to
get device EDS files
with all the mandatory
fields.
17
All the IO Modules
importing are not
having connections.
Import cannot
proceed further
This shall come for
IO modules EDS
files if they do not
have connections in
Connection
Manager
EtherNet/IP/
Modular
Import will abort.
Contact the vendor to
get IO EDS files with
all the Connection
information available.
18
The following IO
Modules does not
have connections
<Rejected Module
name> So the
modules are not
added to the
parsing list
This shall come for
IO modules EDS
files if they do not
have valid
connections in
Connection
Manager.
EtherNet/IP/
Modular
Proceed with the
import by deselecting
the IO modules that
do not have valid
connections. Contact
the vendor to get IO
EDS files with all the
connection
information available
Table 41. Messages - Import of EDS Files (Continued)
Sl
No
Message
Reason
Applicability
Based on Device
Classification
Additional
Information and
Workaround
Summary of Contents for AC 800M
Page 2: ......
Page 3: ...AC 800M EtherNet IP DeviceNet Configuration System Version 6 0 ...
Page 10: ...Table of Contents 10 9ARD000014 600 A ...
Page 18: ...Released User Manuals and Release Notes About This User Manual 18 9ARD000014 600 A ...
Page 22: ...Figure 1 System configuration Device Import Wizard Section 1 Introduction 22 9ARD000014 600 A ...
Page 26: ...Linear Network Section 1 Introduction 26 9ARD000014 600 A ...
Page 46: ...Hot Swap of EtherNet IP Device Section 2 Functional Description 46 9ARD000014 600 A ...
Page 68: ...Figure 22 Enum Values File Section 3 Device Import Wizard 68 9ARD000014 600 A ...
Page 71: ...Section 3 Device Import Wizard File 9ARD000014 600 A 71 Figure 25 EDS Range selection ...
Page 222: ...Auxiliary RS 232 9 Pin D Subminiature Section 8 Hardware Connections 222 9ARD000014 600 A ...
Page 259: ......