Section 4 Configuration
Configuring Logix 5000 series PLC Unit
9ARD000014-600 A
143
The Hardware Editor contains three tabs — Settings, Connections and Unit Status.
The parameters for configuring the Control Logix PLC device are found in the
Settings
tab. Configure the parameters according to the description of parameters
given in
Table 24. Settings for Allen Bradley Control Logix PLC
Parameter
Data Type Unit
Min
Max
Editable
/Read
Only
Description
IP Address
String
-
-
-
Editable
The IP address of the PLC unit on the
network. It must be an IP address on
the same subnet as where the CI873
is placed.
If the IP address is blank, then first
three fields are taken from its parent
CI873 IP address and the fourth is
taken from its hardware tree position.
Upon modification, connection of
CI873 with the PLC unit is re-
established.
Slot Number Dint
-
-
-
Editable
The slot position occupied by the
PLC in the chassis.
ReceiveDat
aFrom
O2TRPI
Dint
ms
10
500
Editable
Requested Packet Interval in
milliseconds for O->T packets.
Upon modification, connection with
the PLC unit is re-established.
ReceiveDat
aFrom
T2ORPI
Dint
ms
10
500
Editable
Requested Packet Interval in
milliseconds for T->O packets.
Upon modification, connection with
the PLC is re-established.
Class 3
Enabled
Enum
-
-
-
Editable
This parameter is to enable/disable
the class 3 support.
Summary of Contents for AC 800M
Page 2: ......
Page 3: ...AC 800M EtherNet IP DeviceNet Configuration System Version 6 0 ...
Page 10: ...Table of Contents 10 9ARD000014 600 A ...
Page 18: ...Released User Manuals and Release Notes About This User Manual 18 9ARD000014 600 A ...
Page 22: ...Figure 1 System configuration Device Import Wizard Section 1 Introduction 22 9ARD000014 600 A ...
Page 26: ...Linear Network Section 1 Introduction 26 9ARD000014 600 A ...
Page 46: ...Hot Swap of EtherNet IP Device Section 2 Functional Description 46 9ARD000014 600 A ...
Page 68: ...Figure 22 Enum Values File Section 3 Device Import Wizard 68 9ARD000014 600 A ...
Page 71: ...Section 3 Device Import Wizard File 9ARD000014 600 A 71 Figure 25 EDS Range selection ...
Page 222: ...Auxiliary RS 232 9 Pin D Subminiature Section 8 Hardware Connections 222 9ARD000014 600 A ...
Page 259: ......