![ABB AC 800M Configuration Download Page 224](http://html.mh-extra.com/html/abb/ac-800m/ac-800m_configuration_2904224.webp)
Appendix A Troubleshooting EDS File
224
9ARD000014-600 A
3
There is more than
one adapter
selected. Please
select one and only
one adapter with
the IO modules and
proceed with the
import process
There are more
than one adapter
selected by the user
which is not
allowed.
Modular
EtherNet/IP/
DeviceNet
Deselect one adapter
to proceed with the
import.
4
An adapter of the
similar name from a
folder other than
the current folder
has been imported.
Please select the
adapter from the
earlier folder or
change the name of
the adapter EDS
being imported and
try again
Adapter file from a
different folder with
the same name is
not allowed. This is
observed during a
re-import.
Modular
EtherNet/IP/
DeviceNet
Import will abort.
During re-import,
select the adapter file
from the folder that
was from the same
location as selected
during fresh import.
5
Please cancel the
process and use a
different/new
Library to import
the revised version
of EDS file.
Major revision has
been changed in
re-import which is
not allowed.
EtherNet/IP/
DeviceNet
Import will abort.
Start a fresh import of
the EDS file in a new
hardware library.
Table 41. Messages - Import of EDS Files (Continued)
Sl
No
Message
Reason
Applicability
Based on Device
Classification
Additional
Information and
Workaround
Summary of Contents for AC 800M
Page 2: ......
Page 3: ...AC 800M EtherNet IP DeviceNet Configuration System Version 6 0 ...
Page 10: ...Table of Contents 10 9ARD000014 600 A ...
Page 18: ...Released User Manuals and Release Notes About This User Manual 18 9ARD000014 600 A ...
Page 22: ...Figure 1 System configuration Device Import Wizard Section 1 Introduction 22 9ARD000014 600 A ...
Page 26: ...Linear Network Section 1 Introduction 26 9ARD000014 600 A ...
Page 46: ...Hot Swap of EtherNet IP Device Section 2 Functional Description 46 9ARD000014 600 A ...
Page 68: ...Figure 22 Enum Values File Section 3 Device Import Wizard 68 9ARD000014 600 A ...
Page 71: ...Section 3 Device Import Wizard File 9ARD000014 600 A 71 Figure 25 EDS Range selection ...
Page 222: ...Auxiliary RS 232 9 Pin D Subminiature Section 8 Hardware Connections 222 9ARD000014 600 A ...
Page 259: ......