Table 22. Cyclic Connection Parameters
Parameter
Default
Value
Data
Type
Read Only /
Editable
Description
Acknowledge
time
16
Int
Editable
It is the amount of time that a producing
node (a DeviceNet slave) waits for an
acknowledgement from the consuming node
(a linking device LD 800DN) before it re-
sends the data.
Send Rate
1000 ms
Int
Editable
This is the background production interval
for cyclic connection. If 1000ms is the Send
Rate, then the device cyclically produces
data every 1000ms.
Inhibit time
1 ms
Int
Editable
This is the new data production inhibit time.
If it is set as 1ms, then the slave produces
the data after every 1ms, even if it has new
data ready before this time elapses.
Cyclic
Connection
Enabled
Depends
on the
device
support
as stated
in its EDS
file
Enum
Editable
Enable or disable the connection. If enabled,
linking device communicates with the device
over the Cyclic connection
Values are: Enabled and Disabled.
Summary of Contents for AC 800M
Page 2: ......
Page 3: ...AC 800M EtherNet IP DeviceNet Configuration System Version 6 0 ...
Page 10: ...Table of Contents 10 9ARD000014 600 A ...
Page 18: ...Released User Manuals and Release Notes About This User Manual 18 9ARD000014 600 A ...
Page 22: ...Figure 1 System configuration Device Import Wizard Section 1 Introduction 22 9ARD000014 600 A ...
Page 26: ...Linear Network Section 1 Introduction 26 9ARD000014 600 A ...
Page 46: ...Hot Swap of EtherNet IP Device Section 2 Functional Description 46 9ARD000014 600 A ...
Page 68: ...Figure 22 Enum Values File Section 3 Device Import Wizard 68 9ARD000014 600 A ...
Page 71: ...Section 3 Device Import Wizard File 9ARD000014 600 A 71 Figure 25 EDS Range selection ...
Page 222: ...Auxiliary RS 232 9 Pin D Subminiature Section 8 Hardware Connections 222 9ARD000014 600 A ...
Page 259: ......