Table 16. Settings for CI873 EtherNet/IP Communication Interface Unit
Parameter
Default Value
Description
Consequence of Change
Configured
Primary IP
address
192.168.0.3
IP address of CI873
when configured in
single or the IP address
of Primary when
configured in
redundant.
CI873 closes all the CIP
connections configured
and re-establishes with the
new IP address.
Configured
Backup IP
address
192.168.0.30
IP address of Backup
CI873 when configured
in redundant.
CI873 re-configures its
Ethernet interface with the
new IP address.
Subnet Mask
255.255.255.0
Net mask
Communication with all the
devices stops. Connection
will be re-established, then
the communication
resumes.
Section 4 Configuration
Adding LD 800DN Linking Device Unit
9ARD000014-600 A
109
Adding LD 800DN Linking Device Unit
This section describes how to insert and configure LD 800DN linking device unit in
Control Builder.
Inserting LD 800DN Linking Device Unit
For inserting a new LD 800DN Linking Device Unit in the hardware tree, follow
these steps:
1.
Right-click the CI873 and select
Insert Unit
. The
Insert Unit
window appears
Summary of Contents for AC 800M
Page 2: ......
Page 3: ...AC 800M EtherNet IP DeviceNet Configuration System Version 6 0 ...
Page 10: ...Table of Contents 10 9ARD000014 600 A ...
Page 18: ...Released User Manuals and Release Notes About This User Manual 18 9ARD000014 600 A ...
Page 22: ...Figure 1 System configuration Device Import Wizard Section 1 Introduction 22 9ARD000014 600 A ...
Page 26: ...Linear Network Section 1 Introduction 26 9ARD000014 600 A ...
Page 46: ...Hot Swap of EtherNet IP Device Section 2 Functional Description 46 9ARD000014 600 A ...
Page 68: ...Figure 22 Enum Values File Section 3 Device Import Wizard 68 9ARD000014 600 A ...
Page 71: ...Section 3 Device Import Wizard File 9ARD000014 600 A 71 Figure 25 EDS Range selection ...
Page 222: ...Auxiliary RS 232 9 Pin D Subminiature Section 8 Hardware Connections 222 9ARD000014 600 A ...
Page 259: ......