Section 2 Functional Description
Status Handling for LD 800DN
9ARD000014-600 A
35
Status Handling for LD 800DN
Table 4. Errors and Warnings of LD 800DN
Bit
Value
Text
Indication Alarm/Event
Severity
Description
13
0x00002000
Connection
Error
Error
Alarm
Medium
Set when the connection
between CI873 and
LD 800DN is failed to
establish or timedout.
31
0x80000000
Device Not
Found
Error
Alarm
High
Set when LD 800DN is
not present in the network
29
0x20000000
Internal
Config Error
Warning
-
-
Set when the
configuration requests, to
configure LD, fails.
27
0x08000000
Duplicate
MAC ID
Error
Alarm
High
Set when one of the
DeviceNet device has the
same MAC ID as
LD 800DN
24
0x01000000
ADR Error
Error
Alarm
High
Set when an error
occurred during auto
device recovery of a
DeviceNet device.
23
0x00800000
No
DeviceNet
Power
Error
Alarm
High
Set when there is no
Network power detected
on the DeviceNet network
22
0x00400000
CAN Bus off
Error
Alarm
High
Set when the CAN
Controller is in the Bus-
Off state
shows all LD 800DN specific Unit Status bits in ErrorAndWarnings and
ExtendedStatus.
Summary of Contents for AC 800M
Page 2: ......
Page 3: ...AC 800M EtherNet IP DeviceNet Configuration System Version 6 0 ...
Page 10: ...Table of Contents 10 9ARD000014 600 A ...
Page 18: ...Released User Manuals and Release Notes About This User Manual 18 9ARD000014 600 A ...
Page 22: ...Figure 1 System configuration Device Import Wizard Section 1 Introduction 22 9ARD000014 600 A ...
Page 26: ...Linear Network Section 1 Introduction 26 9ARD000014 600 A ...
Page 46: ...Hot Swap of EtherNet IP Device Section 2 Functional Description 46 9ARD000014 600 A ...
Page 68: ...Figure 22 Enum Values File Section 3 Device Import Wizard 68 9ARD000014 600 A ...
Page 71: ...Section 3 Device Import Wizard File 9ARD000014 600 A 71 Figure 25 EDS Range selection ...
Page 222: ...Auxiliary RS 232 9 Pin D Subminiature Section 8 Hardware Connections 222 9ARD000014 600 A ...
Page 259: ......