Digital inputs/outputs
Data
Value
Number of channels per device
16 inputs/outputs
Connections
Connector X1 (terminals 4.0 ... 4.7)
Connector X9 (terminals 8.0 ... 8.7)
Division of channels in groups
2 groups of 8 channels each
Group 1: terminals 4.0 ... 4.7
Group 2: terminals 8.0 ... 8.7
Common reference potential ZP
All digital I/O channels of the DA501 and
DA502 module
Common voltage supply
UP (supplies DA501 and DA502 module)
Electrical isolation
Electrical isolation from group to group is no
longer available.
Electrical isolation from DA501 and DA502
(reference ZP) to the rest of the device (refer-
ence M).
On DA501 and DA502, all digital channels
have the same potential ZP.
AGND1 and AGND2 of the analog channels
are internally connected to ZP via PTC resis-
tors.
Configurability of the inputs:
-> Input delay
Typically 0.1 ms, configurable from 0.1 ms to
32 ms
Indication of the input/output signals
1 yellow LED per channel. The LED is ON in
"High" signal state (1 signal)
Input signal voltage (when used as input)
Further information on page 32
.
-> 0 signal
-3 V ... + 5 V
-> 1 signal
+15 V ... + 30 V
Input current per channel
Chapter 1.4.1.3.4.4 “Digital inputs”
Output current / switching frequency / induc-
tive loads
Chapter 1.4.1.3.4.5 “Digital outputs”
Total load current (all DC channels, 4.0..4.7
max. 8A and 8.0…8.7)
max. 8 A
Total load current (all DO channels, 1.0...1.7
max. 4A and 2.0…2.7)
max. 4 A
Total load current (via UP) 16 DO channels
and 16 DC channels
max. 12 A (all UP terminals must be con-
nected)
Max. cable length
Chapter 1.4.1.3.4.4 “Digital inputs”
Chapter 1.4.1.3.4.5 “Digital outputs”
AC31 Adapters
Replacement devices: CPU > Replacement device 07KT9x-AD
2018/09/24
3ADR010122, 8, en_US