Connector / Terminal
Pin
Assignment / Signal
X6 / 4.2
31
AX522 / O2+
X6 / 3.2
32
AX522 / O2- (AGND)
X6 / 4.3
33
AX522 / O3+
X6 / 3.3
34
AX522 / O3- (AGND)
Table 75: Pin assignment AO (X7)
Connector / Terminal
Pin
Assignment / Signal
X7 / 4.4
35
AX522 / O4+
X7 / 3.4
36
AX522 / O4- (AGND)
X7 / 4.5
37
AX522 / O5+
X7 / 3.5
38
AX522 / O5- (AGND)
X7 / 4.6
39
AX522 / O6+
X7 / 3.6
40
AX522 / O6- (AGND)
X7 / 4.7
41
AX522 / O7+
X7 / 3.7
42
AX522 / O7- (AGND)
The outputs on connector X7 cannot be configured as current outputs.
The signals Ix- and Ox- are internally linked to an AGND area. The potential AGND is con-
nected to the potential M via PTC resistors. Potential difference AGND to M
±
1 V maximal.
To enable wire-break detection, each input is internally pulled to "plus" by means of a high-impe-
dance resistor. As a result, the maximum voltage is read when nothing is connected. Do not
replace the AX522 module while voltage is connected.
Fig. 78: Voltage input
1) Electrically isolated power supply of analog sensor
AC31 Adapters