Technical Data of the complete device
Table 97: Supply voltage Vs
Data
Value
Process voltage: Fuse for Vs+
10 A, fast acting
Current consumption:
-> via Vs+
Replacement device: 0.15 A
Existing device DC501-CS31: approx. 60 ... 230 mA
- Inrush current via Vs+ (when
voltage is switched on)
0.06 A²s
Power consumption
5 W
For further information, please refer to the existing documentation
System description Advant Controller 31.
CAUTION!
System damage caused by voltage!
Exceeding the maximum supply or process voltage (>30 V DC) results in per-
manent system damage (destruction).
Table 98: Supply voltage V
Data
Value
Process voltage:
-> Fuse for V+
10 A, fast acting
-> Additional V-/Vs- connections
(GND)
X4 / -0, X4 / -1, X4 / -2, X4 / -3, X4 / -4, X4 / -5, X4 / -6,
X4 / -7, X4 / -8
Current consumption:
-> via V+
Replacement device: 0.15 A incl. load current
Existing device DC501-CS31: approx. 100 mA without
load current
- Inrush current via V+ (when
voltage is switched on)
0.013 A
2
s
Power consumption
220 W
Power consumption outputs
unloaded
6 W
Sensor supply voltage connections X4 / +0, X4 / +1, X4 / +2, X4 / +3, X4 / +4, X4 / +5, X4 /
+6, X4 / +7, X4 / +8
Current sensor supply voltage (all
connections combined)
Replacement device: max. 200 mA
Existing device DC501-CS31: Microfuse 8 A, fast acting
*)
*) The existing device contained an 8 A fuse to be exchanged by the user. The replacement
device has an integrated electronic current limiter instead.
AC31 Adapters
Replacement devices: I/O modules > Replacement unit DC501-CS31-AD
2018/09/24
3ADR010122, 8, en_US